ABB REF615 ANSI 5.0 FP1 Product Manual page 36

Feeder protection and control
Table of Contents

Advertisement

36
R E F 6 1 5 A N S I 5 . 0 F P 1 F E E D E R P R OT E C T I O N A N D C O N T R O L
Table 10. Binary inputs
Description
Operating range
Rated voltage
Current drain
Power consumption
Threshold voltage
Reaction time
Table 11. RTD/mA measurement (XRGGIO130)
Description
RTD inputs
mA inputs
Table 12. Signal output X100: SO1
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry for 0.5 s
Breaking capacity when the control-circuit time constant L/R<40 ms
Minimum contact load
Table 13. Signal outputs and IRF output
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry for 0.5 s
Breaking capacity when the control-circuit time constant L/R<40 ms, at
48/110/220 V DC
Minimum contact load
Supported RTD sensors
Supported resistance range
Maximum lead resistance (three-wire
measurement)
Response time
RTD/resistance sensing current
Operation accuracy
Supported current range
Current input impedance
Operation accuracy
Value
±20% of the rated voltage
24...250 V DC
1.6...1.9 mA
31.0...570.0 mW
16...176 V DC
<3 ms
Value
100 Ω platinum
250 Ω platinum
100 Ω nickel
120 Ω nickel
250 Ω nickel
10 Ω copper
0...2 kΩ
2 kV (inputs to protective earth)
<4 s
Maximum 0.33 mA rms
Resistance
± 2.0% or ±1 Ω
0...20 mA
44 Ω ± 0.1%
±0.5% or ±0.01 mA
Value
250 V AC/DC
5 A
15 A
30 A
1 A/0.25 A/0.15 A
100 mA at 24 V AC/DC
Value
250 V AC/DC
5 A
15 A
15 A
1 A/0.25 A/0.15 A
10 mA at 5 V AC/DC
TCR 0.00385 (DIN 43760)
TCR 0.00385
TCR 0.00618 (DIN 43760)
TCR 0.00618
TCR 0.00618
TCR 0.00427
Temperature
±1°C
10 Ω copper: ±2°C

Hide quick links:

Advertisement

Table of Contents
loading