ABB REF615 ANSI 5.0 FP1 Product Manual page 48

Feeder protection and control
Table of Contents

Advertisement

48
R E F 6 1 5 A N S I 5 . 0 F P 1 F E E D E R P R OT E C T I O N A N D C O N T R O L
Table 49. Phase discontinuity protection (PDNSPTOC)
Characteristic
Operation accuracy
Start time
Reset time
Reset ratio
Retardation time
Operate time accuracy in definite time mode
Suppression of harmonics
Table 50. Phase discontinuity protection (PDNSPTOC) main settings
Parameter
Start value
Operate delay time
Min phase current
Table 51. Residual overvoltage protection (ROVPTOV)
Characteristic
Operation accuracy
Start time
1) 2)
U
= 2 x set Start value
Fault
Reset time
Reset ratio
Retardation time
Operate time accuracy in definite time mode
Suppression of harmonics
1) Residual voltage before fault = 0.0 × U
measurements
2) Includes the delay of the signal output contact
Table 52. Residual overvoltage protection (ROVPTOV) main settings
Parameter
Start value
Operate delay time
Function
PDNSPTOC
PDNSPTOC
PDNSPTOC
Value
Depending on the frequency of the measured current: f
±1.5% of the set value or ±0.002 x U
Minimum
48 ms
Typically 40 ms
Typically 0.96
< 35 ms
±1.0% of the set value or ±20 ms
DFT: -50dB at f = n x f
, f
= 50 Hz, residual voltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000
n
n
Function
ROVPTOV
ROVPTOV
Value
Depending on the frequency of the measured current: f
±2% of the set value
<70 ms
Typically 40 ms
Typically 0.96
<35 ms
±1.0% of the set value or ±20 ms
DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,...
Value (range)
10...100%
100...30000 ms
0.05...0.30 × In
n
Typical
51 ms
, where n = 2, 3, 4, 5,...
n
Value (range)
0.010...1.000 × U
n
40...300000 ms
±2 Hz
n
Step
1
1
0.01
±2 Hz
n
Maximum
54 ms
Step
0.001
1