R E F 6 1 5 A N S I 5 . 0 F P 1 F E E D E R P R OT E C T I O N A N D C O N T R O L
Table 24. Insulation tests
Description
Dielectric tests
Impulse voltage test
Insulation resistance measurements
Protective bonding resistance
Table 25. Mechanical tests
Description
Vibration tests (sinusoidal)
Shock and bump test
Seismic test
Table 26. Environmental tests
Description
Dry heat test
Dry cold test
Damp heat test
Change of temperature test
Storage test
1) For relays with an LC communication interface the maximum operating temperature is +70°C
Table 27. Product safety
Description
LV directive
Standard
Table 28. EMC compliance
Description
EMC directive
Standard
Table 29. RoHS compliance
Description
Complies with RoHS directive 2002/95/EC
Type test value
2 kV, 50 Hz, 1 min
500 V, 50 Hz, 1 min, communication
5 kV, 1.2/50 μs, 0.5 J
1 kV, 1.2/50 μs, 0.5 J, communication
>100 MΩ, 500 V DC
<0.1 Ω, 4 A, 60 s
Type test value
IEC 60068-2-6 (test Fc)
IEC 60255-21-1
IEC 60068-2-27 (test Ea shock)
IEC 60068-2-29 (test Eb bump)
IEC 60255-21-2
IEC 60255-21-3
Type test value
• 96 h at +55ºC
• 16 h at +85ºC1)
• 96 h at -25ºC
• 16 h at -40ºC
• 6 cycles (12 h + 12 h) at +25°C...+55°C,
humidity >93%
• 5 cycles (3 h + 3 h)
at -25°C...+55°C
• 96 h at -40ºC
• 96 h at +85ºC
Value
2006/95/EC
EN 60255-27 (2013)
EN 60255-1 (2009)
Value
2004/108/EC
EN 60255-26 (2013)
Value
Reference
IEC 60255-27
IEEE C37.90-2005
IEC 60255-27
IEEE C37.90-2005
IEC 60255-27
IEC 60255-27
Reference
Class 2
Class 2
Class 2
Reference
IEEE C37.90-2005
IEC 60068-2-2
IEEE C37.90-2005
IEC 60068-2-1
IEEE C37.90-2005
IEC 60068-2-30
IEEE C37.90-2005
IEC60068-2-14
IEEE C37.90-2005
IEC 60068-2-1
IEC 60068-2-2