Table of Contents

Advertisement

3. Low Press 2 Inst – S2 Lo pressure sensor installed (yes or no)
4. Prod Flow Inst – Product flow meter installed (yes or no)
5. Brine Flow Inst – Brine flow meter installed (yes or no)
6. Tank Full Inst – Tank level full sensor installed (yes or no)
7. Tank Empty Inst – Tank level empty sensor installed (yes or no)
8. Time to AutoShut – Auto shutdown after X hours in state FWP (HH:mm:ss)
9. AutoShut Time – Auto shutdown after time (yes or no)
10.AutoShut Tank – Auto shutdown on tank full (yes or no)
11.FWF Duration – FWF duration time (HH:mm:ss)
12.FWF Interval – FWF interval time (HH:mm:ss)
13.AutoStart Tank – Autostart on tank empty (yes or no)
14.Salinity Level – Salinity error level (ppm)
15.Min Pressure – minimum pressure (Bar or PSI)
16.Max Pressure – Maximum pressure (Bar or PSI)
17.Sol. Valve Time – Solenoid valve time (seconds)

Fresh Water Flush button

This button initiates the Fresh Water Flush (FWF) cycle. The cycle can be interrupted by pressing this button
again to stop operation. Note that this button starts the FWF cycle, regardless of whether or not you are
browsing a menu. Note the button has to be pressed down for 5 seconds and released to initiate FWF.
Booster Pump button
Start the booster pump. Press the Start/Stop button to stop operation. Note that this button starts the booster pump,
regardless of whether or not you are browsing a menu.

Shutting Down the Ultra Whisper System

1. Prior to stopping the system, determine if the system will be stored for a period of time or if it will be
operated again soon. Failure to properly flush and or store the system will lead to premature fouling or
drying out of the RO Membrane Element, which is not covered by the Sea Recovery Warranty and is the
liability of the operator of the system. If the system will not be operated within the next month or longer,
perform a long-term storage operation.
a) If the system will be exposed to freezing temperatures, you must follow winterizing procedures. Freezing
temperatures will cause extensive damage if the system is not properly protected.
b) If the system will be operated within the next two weeks, no action is necessary besides winterization
for freezing temperatures.
c) If the system will not be operated within the next two weeks, perform a freshwater flush. If the Sea Recovery
Automatic Freshwater Flush is installed, ensure that the potable water storage tank has fresh potable
water for the freshwater flush to utilize in rinsing the system. If the system does not include an automatic
freshwater flush, perform a manual freshwater flush of the system.
d) If the system will not be operated within the next month or longer, perform a long-term storage
operation.
2. Stop the system by pressing the "START/STOP" button once. As soon as the system shuts down, there will
be a pressure release out of the system and all pressures will drop to zero after 2 minutes.
Danger: Any auxiliary valve in these lines damages the Sea Recovery System if closed during
depressurization or during fresh water flush cycle.
Caution: If pressure remains in the system of 30 psi (2 Bar) or greater in the system refer to your trouble
shooting guide or contact your Sea Recovery dealer.