Emerson SolaHD SDUMBUSCARD Instruction Manual page 21

Uninterruptible power systems. sdu ac - a series comm cards
Table of Contents

Advertisement

ADI Inst:102
UPS Model:
sDU850A
sDU850A-5
sDU500A
sDU500A-5
ADI Inst:104
Rating:
sDU850A:
"120Vac 60Hz 7.1A"
sDU850A-5: "230Vac 50Hz 3.7A"
sDU500A:
"120Vac 60Hz 4.2A"
sDU500A-5: "230Vac 50Hz 2.2A"
ADI Inst:105
Load level
example: Byte=60 the load level is 60%
ADI Inst:106
Battery level
example: Byte=60 the battery level is 60%
ADI Inst:107
Input voltage
example: Byte=120 the input voltage is =120V
ADI Inst:108
Output voltage
example: Byte=120 the output voltage is =120V
ADI Inst:109
Input frequency
example: Byte=60 the input frequency is 60Hz
ADI Inst:110
Output frequency
example: Byte=60 the output frequency is 60Hz
ADI Inst:111
UPS Status-1:
bit 0 is line fail (1 = InV, 0 = LIne)
bit 1 is low battery (1 = BAt LoW, 0 = noRMAL)
bit 2 reserved
bit 3 reserved
bit 4 reserved
bit 5 LoAD stAtUs(1 = oVeR LoAD, 0 = noRMAL)
bit 6 reserved
bit 7 sD MoDe DIsPLAY
ADI Inst :112
UPS Status-2:
bit 0 reserved
bit 1 BAt stAtUs(1 = BAD, 0 = noRAML)
bit 2 test MoDe (1 = test, 0, noRMAL)
bit 3 Buzzer silence on/off (1= silence)
bit 4 PRe-sD CoUnt MoDe (1 = ACtIVe)
bit 5 sCHeDULe CoUnt MoDe (1 = ACtIVe)
bit 6 DIsBLe no LoAD sHUtDoWn (1 = ACtIVe)
bit 7 reserved
ADI Inst: 113
UPS model number
32H =500VA 120V
39H =500VA 230V
52H =850VA 120V
59H =850VA 230V
ADI Inst: 114
PRE-SD min Time
UPs echo PRe-sD count down time----min
ADI Inst: 115
PRE-SD sec Time
UPs echo PRe-sD count down time----sec
Buzzer silence off = Alarm enabled
Buzzer silence on = Alarm Disabled
sDU AC - A seRIes CoMM CARDs InstRUCtIon MAnUAL | 17