Summary of Contents for olympia electronics BS-1632
Page 1
Conventional 2, 4 and 6 zone Fire Alarm Panels Thank you for your trust in our products Olympia Electronics - European manufacturer GENERAL The family of fire detection panels consist of 3 types (2, 4 and 6 zone) with identical operation and indications. The panels have 2 independent siren outputs, Alarm, Fault Relay and a programmable AUX relay.
Indication LED description The schematic shows the control keyboard and the indication plate of a 6 zone BS-1636 panel. Starting from the top left side we can see 4 indicators marked 'General'.The 'Disable' LED lights in every DISABLE condition. The 'Test' LED lights in every TEST condition .The panel does not have a test condition as specified in paragraph 11 of EN 54-2.
Page 3
Access level 2: "34” Includes all the functions that the user can do and an access code is required. The code is , it is the same for all panels and can not be changed. The functions that can be implemented using this code are the following: Evacuate: Gives evacuate signal to the panel.
Page 4
Program Siren delay. If we want to program the delay of the sirens we must enter the technical code ( 364 ) and then press the key '4'. The 'General fault', 'General Disable' and 'General alarm' LEDs start to blink. The Alarm, the Fault/Disable LED of zone 1 and Fault/Disable LED of zone 2 show the programmed delay of the sirens according to the table below.
Page 5
Connections The three panels of the family have the same connections. The main differences in these panels is the number of the available zones and the number of the relays zones. The common outputs, the maximum consumption and the operation procedures are identical for all the panels. Connecting detectors and break-glass call points to zones By default each zone terminal block has a preinstalled terminal resistor (8Κ2).
Page 6
Siren - Sounder Connections Each panel offers 2 independent circuits for connecting sirens, bells or other devices that need 24VDC in order to operate. Each circuit can supply a maximum of 300mA. Each terminal block by default has a pre-installed terminal resistor (8Κ2).
Figure 8 . Battery connection The battery compartment has the appropriate dimensions for Α-920 batteries of Olympia Electronics. The charging unit on PCB is also calculated for the specific batteries. Replace them only with batteries of the same type.
1 cm 220-240V AC Fuse: T630mAL250V (5x20) Figure 9. Panels connection with 220-240V AC Figure 8. Panels connection with 220-240V AC Battery disposal s not allowed to discard batteries into common trash bins, they must be discarded only battery recycling points. Warnings 1.
Technical Specifications BS-1632 BS-1634 BS-1636 2 zone fire 4 zone fire 6 zone fire detection panel detection panel detection panel Mains power supply 220-240V AC / 50-60Hz Consumption 50VA Battery type Two 12V Lead acid sealed 2.6Ah Charging circuit Stabilized power supply 27.6V / max. 400mA...
Page 10
Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of defection.