olympia electronics BS-627 Manual

4 zone panel with one extinguish output

Advertisement

4 zone panel with one extinguish output
Thank you for purchasing this product of Olympia Electronics. A European manufacturer.
GENERAL
The panel has :
- One fire extinguish output monitored for open and short circuit. The output can operate with actuators or electro valves.
-Two cross zones for fire detectors.
- One zone for a manual call point to start the extinguish procedure.
- One zone for a manual call point to cancel the extinguish procedure.
- Three modes of operation
- The panel has two independent siren outputs.
- One contact relay for fault status.
- Two fully programable relay contacts.
-Terminals to communicate with conventional fire detection panels.
The battery Α-986 (12V/7Ah) is required for the operation of the panel.
All functions and indications are according to European Norms ΕΝ 12094-1, EN 54-2, EN 54-4.
Page 1 from 12
BS-627
Control Keyboard and
indication leds
Press for extinguish
cancellation
High Quality European based Manufacturers
Insert the included
restoration key
Insert the key to access
the internal of the panel
Press for immediate
extinguishing
921627000_09_010

Advertisement

Table of Contents
loading

Summary of Contents for olympia electronics BS-627

  • Page 1 High Quality European based Manufacturers BS-627 4 zone panel with one extinguish output Thank you for purchasing this product of Olympia Electronics. A European manufacturer. GENERAL The panel has : - One fire extinguish output monitored for open and short circuit. The output can operate with actuators or electro valves.
  • Page 2: Led Indicator Description

    LED Indicator description The picture shows the control keyboard and the indication plate of a BS-627 panel. Starting from the top left side are : The 'Power' LED lights when the panel is powered and blinks, in mains failure. Also in the top left side we can see three indicators marked 'General'.
  • Page 3 To restore the button to its previous position you must use the included black plastic key. Place the key in the respective hole, turn it at 90° and pull it until the button is restored. Cancel - extinguish deactivation: By pressing the red button (panic type) on the front side of the panel (side picture) the extinguish output is deactivated.
  • Page 4 mode and to store the settings in memory press the key '6’ or do not press any key for more than 30 seconds. The system will conduct an automatic RESET and will enter normal operation mode. This delay is current for all the zones, but if the yellow activation button is pressed, the delay will be 5 seconds.
  • Page 5 RF= fault relay Το Relay1 terminal of a BSR-2104, or BSR-2114 To the BS-63X zone 5k6/0.5W BS-527 5k6/0.5W BS-527 12k/0.5W 12k/0.5W 5k6/0.5W BS-537 470Ω/0.5W 5k6/0.5W BS-533 Figure 1. Connecting devices to BS-627 panel OUT IN Page 5 from 12 921627000_09_010...
  • Page 6 Using Actuators. You can connect actuators in series. If you use 1 or 2 actuators you must connect a resistor 2.7Ohm / 5W in series as shown below on the right. If you use 3 or 4 actuators you just connected them in series. The maximum number of actuators are 4.
  • Page 7 1. OUTPUT +A,-A. This output is used only for production proposes. This must not be used by any other technician but only technician from olympia electronics. CONNECTION OPTIONS IN ADDRESSABLE OR CONVENTIONAL PANEL For connection on an addressable panel jumpers must be placed as shown on picture 1.
  • Page 8: Installation

    INSTALLATION The installation of the panel must be carried out by qualified personnel only. Disconnect power before servicing. Never insert or remove boards or componets with the power on. During installation use grounded antistatic wrist band to protect this equiment form ESD. The panel must be installed permanetly.
  • Page 9 2. During the installation the connections to the mains power supply and the battery must be done after all other connections are finished. 3. The panel connection with the mains supply must be done via a10A external fuse or an automatic circuit breaker rated at 10A.This fuse has to be a separate, labeled fuse.
  • Page 10: Technical Specifications

    Technical Specifications BS-627 4 zone panel with one extinguish output Mains power supply 220-240V AC 50/60Hz Consumption 100VA Battery type One or two 12V Lead acid sealed 7Ah maximum Charging circuit Stabilized power supply 13.8V / max. 400mA Autonomous duration...
  • Page 11 Technical Specifications The optional function of the panel according to the room EN 54-2 is: Operation panel functions (Fire alarm device(s)) paragraph 7.8 ( EN 54-2 ) Components of the panel have been selected for the intended purpose, and are expected to opetate within their specification when the environmental conditions Design outside the cabinet of the panel comply with class 3k5 of EN 60721-3-3:1995...
  • Page 12 Certification The panel BS-627 is certrified from HEEQAC. Also HEEQAC controls the production under CPR number: 0848-CPR-005. Below is the marking: Page 12 from 12 921627000_09_010...

Table of Contents