Configuration Coaxial Probe; Lower Range Value [4Ma]; Span 0 - Tecfluid LTDR series Instruction Manual

Guided radar level transmitters
Table of Contents

Advertisement

It is recommended that the upper range value stays within the measuring range [M]
(see figure 10).
Change DIP switch position 3 to on/1.
DIP SWITCH POSITION
1
2
DIP SWITCH SETTINGS
0
0
Press the push button.
LED will remain green briefly while the upper range value setting is being executed.
Once it has been executed successfully, the LED will return to blinking alternately green
and red.
Set all the DIP switch positions to 0 as indicated in figure 7. Start from position 1 and
move towards position 8.
DIP SWITCH POSITION
1
2
DIP SWITCH SETTINGS
0
0
the LED will change to blinking green
Tighten the housing cover properly by turning it clockwise.
6

CONFIGURATION COAXIAL PROBE

The coaxial probe has a very robust and reliable measurement performance in almost any
application without further configuration. For basic configuration only the range values for
the analog current output have to be set.
6.1

Lower range value [4mA]; SPAN 0%

Set the DIP switch positions to the 0/1 sequence in figure 8. Start from position 8 and
move towards position 1.
DIP SWITCH POSITION
1
2
DIP SWITCH SETTINGS
0
0
Fill the liquid into the tank up to the level where you want to position the lower range
value [4mA]; span 0%.
It is recommended that the lower range value stays within the measuring range [M] (see
figure 10).
Press the push button.
3
4
5
6
7
8
1
0
0
0
1
1
3
4
5
6
7
8
0
0
0
0
0
0
3
4
5
6
7
0
1
0
0
1
DESCRIPTION
upper range value [20mA]; SPAN 100%
DESCRIPTION
measuring mode
8
DESCRIPTION
1
lower range value [4mA]; SPAN 0%
Figure 7
Figure 8
9