Where:
Accept Mode: Activates Accept mode, where all new keys will be stored into memory as Normal
keys.
Add Keys Mode: Activates Add Normal and Blocking Keys mode on the controller. See paragraph
7.1 for details.
Add Master Keys Mode: Activates Add Master Keys mode. See paragraph 7.2 for details.
Erase Keys Mode: Erases keys touching the Reader, from the keys database. See paragraph 7.3
for details.
Note: When Add Keys, Add Master Keys or Erase Keys mode is selected, an additional pop-up is
displayed, warning that this mode will automatically be terminated, if the interval between keys
reaches 16 s.
Export Keys to File: Exports the keys database from controller memory into a file on the local
computer running the Web interface.
Browse...: Selects a file on the local computer for subsequent keys import.
Import Keys from File: Imports the (previously exported) file into controller key database. The
previous contents of keys database will be overwritten and lost.
5.5
Controller Setup Tab.
Controller Setup tab allows to set up controller operational parameters.
Lock Type: Electric Latch, Electromagnetic, or Electromechanical.
Readers Protocol: Select key code transmission protocol. For Wiegand protocol, the controller
automatically detects the bit width (26, 34, 42 or 50).
Fire Alarm Input: Enables emergency door unlocking when EX.OPEN input signal is asserted.
Built-in Beeper: Enables/disables the built-in beeper.
Opening Time: Duration of the impulse sent into the lock to unlock the door. Depending on Lock
Type, the impulse can be active-low or active-high.
Opening Check Time: Maximum time after access has been granted till the door is open. The
door opened after this interval is considered Forced. If Opening Check Time is shorter than Opening
Time, -- Opening Time is used for this function.
Closing Check Time: Maximum time while the door stays open. If within Closing Check Time
the door has not closed, a Door Held event is generated into the log. To disable Closing Check, set
this parameter to 0.
After setup is complete, save the parameters by pressing Save button.