Panasonic 2WAY Multi Technical & Service Manual page 167

Troubleshooting. gas heat pump, air conditioner.
Hide thumbs Also See for 2WAY Multi:
Table of Contents

Advertisement

Correction example b)
The adjustment value is 10°BTDC, but the observed value was 13° BTDC. Press the UP (S005) or DOWN
(S006) key to set a correction of -3 in relation to the current "   " (ignition timing offset) value.
i)
Display the current "   " (ignition timing
offset) value, and check it. The current value is
zero (0).
The display for "    " will be as shown at
right.
ii) With "   " (ignition timing offset)
displayed, press the SET key (S007) for one
second or more.
The TEST/WARNING LED (D052) will light,
and LEVEL LED (D053) will fl ash.
iii) Press the UP (S005) or DOWN (S006) key to
set a correction of -3 in relation to the current
value checked in "ii)."
The display will show "     " (right
fi gure).
Caution: The display example at right is an
example for when the current value
checked in "i)" is zero (0).
If the current value is "2" and a -3
correction is set in relation to that
value, the value will become "-1"
after the setting is made. The display
will show "     " (fi gure below
right).
iv) With "     " (right fi gure) displayed,
press the SET key (S007) for one second or
more. The TEST/WARNING LED (D052)
will go out, and LEVEL LED (D053) will
light. The ignition timing offset mode will
be cancelled, and the setting process will be
ended.
V–48

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents