Panasonic 2WAY Multi Technical & Service Manual page 156

Troubleshooting. gas heat pump, air conditioner.
Hide thumbs Also See for 2WAY Multi:
Table of Contents

Advertisement

3) System address setting (Level 2)
Rejection conditions
Setting start operation method
Setting change operation method : After entering the setting start operation mode, operating the UP (S005)
Example: 

Setting confi rm operation method : After entering the setting start operation or setting change operation
Setting cancel operation method
Setting range
4) Number of connecting indoor units setting (Level 2)
Rejection conditions
Setting start operation method
Setting change operation method : After entering the setting start operation mode, operating the UP (S005)
Example: 

Setting confi rm operation method : After entering the setting start operation or setting change operation
Setting cancel operation method
Setting range
(*) The number of indoor units that can be connected is restricted separately by each model.
5) Gas type setting (Level 2)
Rejection conditions
Setting start operation method
Setting change operation method : After entering the setting start operation mode, operating the UP (S005)
Example: 

Setting confi rm operation method : After entering the setting start operation or setting change operation
Setting cancel operation method
Setting range
0
Propane G31
1
2
Natural gas G20
3
Natural gas G25
4
: Not accepted during indoor operation
: Press the SET (S007) key for one second.
and DOWN (S006) keys makes it possible to change the setting values.
(TEST/WARNING LED light)
: When pressing the UP (S005) key
: When pressing the DOWN (S006) key
completed, press the SET (S007) key for one second. (TEST/
WARNING LED off)
: Press the HOME (S004) key for one second before confi rming setting.
: 01 to 31
: Not accepted during indoor operation
: Press the SET (S007) key for one second.
and DOWN (S006) keys makes it possible to change the setting values.
(TEST/WARNING LED light)
: When pressing the UP (S005) key
: When pressing the DOWN (S006) key
completed, press the SET (S007) key for one second. (TEST/
WARNING LED off)
: Press the HOME (S004) key for one second before confi rming setting.
: 00
Not set
01 to 48
Number of indoor unit connected in same system 1 to 48 units*
: Not accepted during indoor operation
: Press the SET (S007) key for one second.
and DOWN (S006) keys makes it possible to change the setting values.
(TEST/WARNING LED light)
: When pressing the UP (S005) key
: When pressing the DOWN (S006) key
completed, press the SET (S007) key for one second. (TEST/
WARNING LED off)
: Press the HOME (S004) key for one second before confi rming setting.
: 00 to 0F





V–37