Panasonic 2WAY Multi Technical & Service Manual page 142

Troubleshooting. gas heat pump, air conditioner.
Hide thumbs Also See for 2WAY Multi:
Table of Contents

Advertisement

Model Type Display: No. 03 (Level 0) <  >
This function is used to display the outdoor unit model type.
It may also be used for the double-speed setting (fast-forwarding the forced 3-minute off timer).
Operating the UP (S005) and DOWN (S006) keys causes the menu to change.
1) Model type display (Level 0)
Outdoor unit model types are displayed in the following way.
Not set
45.0kW models
56.0kW models
71.0kW models
85.0kW models
2) Double-speed setting (Level 0)
Operating method : Pressing the SET (S007) key for one second in the model type display mode moves to
the double-speed setting display. (TEST/WARNING LED light)
Releasing method : Press the SET (S007) key for one second in the double-speed setting mode.
(TEST/WARNING LED off)
Operation
: The 3-minute off time timer counts at 10 times or greater speed than normal.
The forced setting in progress display appears during the double-speed setting. (TEST/
WARNING LED light)
Display





V–23