E06 Outdoor Unit Receive Failure From Indoor Unit - Panasonic 2WAY Multi Technical & Service Manual

Troubleshooting. gas heat pump, air conditioner.
Hide thumbs Also See for 2WAY Multi:
Table of Contents

Advertisement

E06 Outdoor Unit Receive Failure from Indoor Unit

1) When the indoor unit is connected
Error detection method
An error is determined when no indoor unit transmission (response) is received for 3 minutes.
• Indoor unit power is OFF.
• Indoor unit DISP pin (CN063/CN072) is short-circuited.
• Indoor/outdoor operation wiring is short-circuited or broken.
• Indoor unit signal output board (option board) is defective.
Troubleshooting
1
Indoor power
1-1 Is the indoor unit power OFF?
source
2
Indoor/outdoor operation wiring broken or short-circuited?
Indoor/outdoor
2-1
(See "5. Reference Document")
operation wiring
3
Is the DISP pin (CN063/CN071) or inspection pin (CN062/
3-1
Indoor control
CN071) on the indoor control board short-circuited?
board
Is an option board (CN060) or wireless remote controller
3-2
(CN041) connected to the indoor control board?
Does E06 disappear several minutes after disconnecting
said connector on the indoor control board? (When
3-3
controlling with two remote controllers and the wireless
remote controller is the main, set the other remote
controller as the main).
Replace the removed option board or wireless remote controller operating unit, wiring and
3-4
all.
3-5 Indoor control board failure → Replace board
● The designation (/) is used in the table to indicate indoor boards for DC and AC motor models.
● There is no TEST pin on the indoor board for AC motor models.
● For board and Electrical Wiring Diagram, see Chapter 6.
• Outdoor main board: page VI-2
• Outdoor power board: page VI-3
• Converter board: VI-4
• Indoor control board for DC motor models: page VI-5
• Outdoor Unit Electrical Wiring Diagram: page VI-6
● See instructions packaged with servicing indoor board for procedure on replacing indoor control board.
2) When the water heat exchange unit is connected
Error detection method
An error may be assumed when communication (response) from the water heat exchanger unit is not received
by the outdoor unit for 3 minutes.
• When power is not being supplied to the water heat exchanger unit.
• When the outdoor unit address set for the water heat exchanger unit and the outdoor unit do not match up.
• When an error occurs with the indoor/outdoor operation wiring (short-circuit, severed wires, ground.)
• When electrical voltage is applied to the indoor/outdoor operation wiring.
• When affected by noise.
• When the water heat exchanger unit's control board or peripheral equipment is defective.
Troubleshooting
1
Is electricity being supplied to the water heat exchanger
Unit power
1-1
unit?
supply
2
Setting
Do the address settings for the water heat exchanger unit
switches
2-1
and outdoor unit match up?
IV–41
Yes Turn power ON
No
2-1
Yes Repair wiring
No
3-1
Yes Eliminate short-circuit
No
3-2
Yes 3-3
No
3-5
Yes 3-4
3-5
No
Yes 2-1
No
Switch on the power
Yes 3-1
Make sure the water
heat exchanger SW14
No
and the outdoor unit
setting match up