Siemens SINAMICS DCP Manual page 66

Dc/dc power converter
Hide thumbs Also See for SINAMICS DCP:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
p2039
Select debug monitor interface / Debug monit select
CU_DCP
Can be changed: U, T
Data type: Unsigned16
Min
0
Description:
Sets the serial interface for the debug monitor.
With p2039 = 1, the serial interface COM2 (X179) is set.
Other values are not permitted.
p2040
Fieldbus interface monitoring time / Fieldbus t_monit
CU_DCP
Can be changed: U, T
Data type: FloatingPoint32
Min
0 [ms]
Description:
Sets the monitoring time to monitor the process data received via the fieldbus interface.
If no process data is received within this time, then an appropriate message is output.
Dependency:
Refer to: F01910
Note:
p2040 = 0:
Monitoring is de-activated.
p2042
PROFIBUS Ident Number / PB Ident No.
CU_DCP
Can be changed: T
Data type: Integer16
Min
0
Description:
Sets the PROFIBUS Ident Number (PNO-ID).
SINAMICS can be operated with various identities on PROFIBUS. This allows the use of a PROFIBUS GSD that is
independent of the device (e.g. PROFIdrive VIK-NAMUR with Ident Number 3AA0 hex).
Value:
0:
1:
Note:
Every change only becomes effective after a POWER ON.
r2043.0...2
BO: IF1 PROFIdrive PZD state / IF1 PD PZD state
CU_DCP
Can be changed: -
Data type: Unsigned8
Min
-
Description:
Displays the PROFIdrive PZD state.
Bit field:
Bit
00
02
Dependency:
Refer to: p2044
Note:
When using the "setpoint failure" signal, the bus can be monitored and an application-specific response triggered
when the setpoint fails.
p2044
IF1 PROFIdrive fault delay / IF1 PD fault delay
DCP_CTRL
Can be changed: U, T
Data type: FloatingPoint32
Min
0 [s]
Description:
Sets the delay time to initiate fault F01910 after a setpoint failure.
The time until the fault is initiated can be used by the application. This means that is is possible to respond to the
failure while the drive is still operational (e.g. emergency retraction).
66
SINAMICS
VIK-NAMUR
Signal name
Setpoint failure
Fieldbus oper
Max
3
Max
1999999 [ms]
Max
1
Max
-
1 signal
Yes
Yes
Max
100 [s]
Access level: 4
Func. diagram: -
Factory setting
1
Access level: 3
Func. diagram: 9310
Factory setting
100 [ms]
Access level: 3
Func. diagram: -
Factory setting
0
Access level: 3
Func. diagram: 2410
Factory setting
-
0 signal
No
No
Access level: 3
Func. diagram: 2410
Factory setting
1 [s]
SINAMICS DCP