6-6-5 Final Installation Checks
Are there scratches or dents on the existing pipes?
Is it possible to operate the existing air conditioner?
• After the existing air conditioner is operated in cooling
mode for approx. 30 minutes or longer,* recover the
refrigerant
• For cleaning the pipes and recovering oil
• Refrigerant recovery: Pump down method
Was largely discolored ora large quantity
of remains discharged? (When the oil
deteriorates, the color of the oil changes to
a muddy or black color.)
Connect the indoor/outdoor units to the existing pipe.
• Use a flare nut attacheindoor/outdoor units. (Do not
existing pipe.)
• Re-machine the flare machining size to size for R32.
Existing piping
The following settings are required when using a pipe Ø19.1 mm as the existing piping at the gas pipe side.
Steps taken to s pport existing piping
1. Cut J805 (Jumper).
2. Set the circuit breaker to the ON position to turn on the power.
Curing manner
Pinching
Pinching or
Taping
NO
YES
NO
- 34 -
YES
Existing pipes: Cannot be used.
• Use new pipes.
NO
YES
Clean the pipes or use new pipes.
Jumper wires