9-1. Calling of error history

<Contents>
The error contents in the past can be called.
<Procedure>
1
Push
+
buttons simultaneously for
4 seconds or more to call the service check mode.
Service Check goes on, the item code 01 is displayed,
and then the content of the latest alarm is displayed. The
number and error contents of the indoor unit in which an
error occurred are displayed.
2
In order to monitor another error history, push the set
temperature
/
No. (Item code).
(Latest) → Item code
Item code
NOTE : 4 error histories are stored in memory.
3
Pushing
button returns the display to usual display.
REQUIREMENT
Do not push
button, otherwise all the error histories of
the indoor unit are deleted.
(Group control operation)
In a group control, operation of maximum 8 indoor units can be controlled by a remote controller.
The indoor unit connected with outdoor unit (Individual/Master of twin) controls room temperature according to
setting on the remote controller.
<System example>
OUT
OUT
IN
IN
1-1
Remote controller
1. Display range on remote controller
The setup range (Operation mode/Air volume select/Setup temp) of the indoor unit which was set to the
master unit is reflected on the remote controller.
2. Address setup
Turn on power of the indoor unit to be controlled in a group within 3 minutes after setting of automatic
address.
If power of the indoor unit is not turned on within 3 minutes (completion of automatic address setting), the
system is rebooted and the automatic address setting will be judged again.
1) Connect 3 In/Out cables surely.
2) Check line address/indoor address/group address of the unit one by one.
3) The unit No. (line/indoor gout address) which have been set once keep the present status as a rule if the
unit No. is not duplicated with one of another unit.

9. SETUP AT LOCAL SITE AND OTHERS

buttons to change the error history
(Old)
OUT
Master
IN
2-1
3-1
<Operation procedure>
OUT
IN
4-1
- 64 -
FILE NO.SVM-18044-2
1
2
3
Returned to usual display
OUT
IN
7-1
Max. 8 units