Requirements
● You have assigned symbolic names to the tags you want to use on your website in
● In the Inspector window under "Properties > General > Web server", you have at least
● You completed all necessary communication settings (IP address parameter, subnet
● You have downloaded the configuration.
● You created your user page in an HTML editor of your choice:
Creating user pages
You can use any HTML editor to create your own user page(s). Make sure that your HTML
code complies with the standards of the W3C (World Wide Web Consortium), because
STEP 7 does not check the HTML syntax in any way.
Proceed as follows:
1. Create the HTML file for your user page with an HTML editor.
2. Store the HTML file and all associated source files (e.g., *.gif, *.jpg, *.js, etc.) on your
3. Call the "WWW" instruction in STEP 7 and program it (see chapter Programming the
4. Configure the user page in STEP 7 (see chapter Configuring user pages (Page 55)). This
5. Open your user page with your display device by means of a web browser in the Web
Web server
Function Manual, 01/2013, A5E03484625-01
STEP 7 .
– activated the Web server.
– entered a user in the user list.
– assigned read-only or read and write permissions to this (and additional) users (see
chapter Properties of the Web server (Page 9)).
mask, etc.).
– Automatic HTML pages, if you want to disable control of the page layout by means of
the user program (requires at least one call of SFC 99)
– Manual HTML pages, if you want to enable control of the page layout by means of the
user program (cyclical call of SFC 99 required)
To read out data from the S7-1500 with your HTML code, integrate the AWP commands
as HTML comments.
display device and write down the storage path.
WWW instruction (Page 56)).
way you compile the contents of your HTML file, among other things, into data blocks in
STEP 7.
server of the CPU.
Note
Comprehensive HTML pages, especially those with a lot of images, take up a lot of
memory in the load memory. Make sure you select a SIMATIC memory card with
sufficient memory to provide ample load memory.