Other Functions

6-7

Other Functions

6-7-1

Motor Protection Characteristics (n33 and n34)

n33
Motor Protection Characteristic Selection
Setting
0 to 2
range
Set Values
Value
0
Protection characteristics for general-purpose induction motors
1
Protection characteristics for Inverter-dedicated motors
2
No protection
n34
Setting
1 to 60 (min)
range
Set Values
The following description provides information on the other functions and
parameter settings of the Inverter.
This parameter setting is for motor overload detection (OL1).
Unit of
setting
• This parameter is used to set the electric thermal characteristics of the
motor to be connected.
• Set the parameter according to the motor.
• If a single Inverter is connected to more than one motor, set the
parameter to 2 for no protection. The parameter is also disabled by setting
n32 for rated motor current to 0.0. To protect each motor from overload,
be sure to take an appropriate measure such as the installation of a
thermal relay.
Motor Protection Time
Unit of
setting
• This parameter is used to set the electronic thermal protection constant of
motor overload detection OL1.
• The default setting does not need any changes in normal operation.
• To set the parameter according to the characteristics of the motor, confirm
the thermal time constant with the motor manufacturer and set the
parameter with some margin. In other words, set the value a little shorter
than the thermal time constant.
• To detect motor overloading more quickly, reduce the set value, provided
that it does not cause any application problems.
Changes during
operation
1
Default setting
Description
Changes during
operation
1 min
Default setting
Chapter 6-7
No
0
No
8
79