Download Print this page

Specifications - Honeywell Spyder PUL1012S Manual

Lon, vav/unitary controllers
Hide thumbs Also See for Spyder PUL1012S:

Advertisement

SPECIFICATIONS

General Specifications
Rated Voltage: 20–30 Vac; 50/60 Hz
Power Consumption:
100 VA for controller and all connected loads (including the
actuator on models PVL0000AS, PVL4022AS, and
PVL6436AS)
Controller Only Load: 5 VA maximum; models PUL1012S,
PUL4024S, PUL6438S, PVL4024NS, and PVL6438NS.
Controller and Actuator Load: 9 VA maximum; models
PVL0000AS, PVL4022AS, and PVL6436AS
External Sensors Power Output: 20 Vdc ±10% @ 75 mA
maximum
VAV Operating & Storage Temperature Ambient Rating
(models PVL0000AS, PVL4022AS, PVL4024NS,
PVL6436AS, and PVL6438NS):
Minimum 32 F (0 C); Maximum 122 F (50 C)
Unitary Operating & Storage Temperature Ambient Rating
(models PUL1012S, PUL4024S, and PUL6438S):
Minimum -40 F (-40 C); Maximum 150 F (65.5 C)
Relative Humidity: 5% to 95% non-condensing
LED: Provides status for normal operation, controller download
process, alarms, manual mode, and error conditions
Velocity Pressure Sensor (Models
PVL0000AS, PVL4022AS, PVL4024NS,
PVL6436AS, and PVL6438NS only)
Operating Range: 0 to 1.5 in. H
Series 60 Floating Actuator (PVL0000AS,
PVL4022AS, and PVL6436AS)
Rotation Stroke: 95° ± 3° for CW or CCW opening dampers
Torque Rating: 44 lb-in. (5 Nm)
Run Time for 90° rotation: 90 seconds at 60 Hz
Operating Temperature: -4 F to 140 F (-20 to 60 C)
Real Time Clock
Operating Range: 24 hour, 365 day, multi-year calendar
including day of week and configuration for automatic day-
light savings time adjustment to occur at 2:00 a.m. local
time on configured start and stop dates
Power Failure Backup: 24 hours at 32 to 100° F (0 to 38° C),
22 hours at 100 to 122° F (38 to 50° C)
Accuracy: ±1 minute per month at 77 F (25 C)
Digital Input (DI) Circuits
Voltage Rating: 0 to 30 Vdc open circuit
Input Type: Dry contact to detect open and closed circuit
Operating Range: Open circuit = False; Closed circuit = True
Resistance: Open circuit > 3,000 Ohms; Closed circuit < 500
Ohms
Digital Triac Output (DO) Circuits
Voltage Rating: 20 to 30 Vac @ 50/60Hz
Current Rating: 25 mA to 500 mA continuous, and
800 mA (AC rms) for 60 milliseconds
Analog Output (AO) Circuits
Analog outputs can be individually configured for current or
voltage.
O (0 to 374 Pa)
2
SPYDER® LON PROGRAMMABLE, VAV/UNITARY CONTROLLERS
ANALOG CURRENT OUTPUTS:
Current Output Range: 4.0 to 20.0 mA
Output Load Resistance: 550 Ohms maximum
ANALOG VOLTAGE OUTPUTS:
Voltage Output Range: 0 to 10.0 Vdc
Maximum Output Current: 10.0 mA
Analog outputs may be configured as digital outputs and
operate as follows:
– False (0%) produces 0 Vdc, (0 mA)
– True (100%) produces the maximum 11 Vdc, (22 mA)
Universal Input (UI) Circuits
See Table 2 for the UI circuit specifications.
Table 2. Universal input circuit specifications.
Input
Type
Room/Zone
20K Ohm
Discharge Air
NTC
Outdoor Air
Temperature
Outdoor Air
C7031G
Temperature
C7041F
PT1000
(IEC751 3850)
TR23
500 Ohm
Setpoint
to
Potentiometer
10,500 Ohm
Resistive Input Generic
Voltage
Transducer,
Input
Controller
Discrete Input
Dry Contact
closure
Counter/Meter Max. frequency: 15 Hz
b
Pulse Input
a
C7031G and C7041F are recommended for use with these
controllers, due to improved resolution and accuracy when
compared to the PT1000.
b
One Universal Input (UI-1*) on the PUL1012S, PUL4024S,
PVL4022AS, and PVL4024NS is user selectable as a fast
digital pulse meter.
BEFORE INSTALLATION
The controller is available in eight models (see Table 1).
Review the power, input, and output specifications on page 3
before installing the controller.
— Hardware driven by Triac outputs must have a minimum
current draw, when energized, of 25 mA and a maximum
current draw of 500 mA.
3
Sensor
Operating
Type
Range
-40 F to 199 F
(-40 C to 93 C)
-40 F to 120 F
a
(-40 C to 49 C)
-40 F to 250 F
a
(-40 C to 121 C)
-40 F to 199 F
(-40 C to 93 C)
-4° DDC to +4° DDC
(-8° DDF to +7° DDF)
or
50 F to 90 F
(10 C to 32 C)
100 Ohms to 100K Ohms
0–10 Vdc
Open Circuit > 3000 Ohms
Closed Circuit < 3000 Ohms
Min. pulse width: 20 ms
Max. chatter 5 ms
63-2685—03

Hide quick links:

Advertisement

loading