Determination of installation location: The controller shall be installed in a place with
sufficient air flow through the radiators of the controller and a minimum clearance of
150 mm from the upper and lower edges of the controller to ensure natural thermal
convection. Please see Figure 2-1: Mounting
CAUTION: If the controller is to be installed in an enclosed box, it is
important to ensure reliable heat dissipation through the box.
Step 2:Connect the system in the order of ❶battery ❷ load ❸PV array in
accordance with Figure 2-2,"Schematic Wiring Diagram" and disconnect the system in
the reverse order❸❷❶.
CAUTION: While wiring the controller do not close the circuit breaker or
fuse and make sure that the leads of "+" and "-" poles are connected
correctly.
CAUTION: A fuse which current is 1.25 to 2 times the rated current of the
controller, must be installed on the battery side with a distance from the
battery not greater than 150 mm.
CAUTION: If the controller is to be used in an area with frequent lightning
strikes or unattended area, it must install an external surge arrester.
CAUTION: If an inverter is to be connected to the system, connect the
inverter directly to the battery, not to the load side of the controller.
Step 3:Grounding
XTRA N series is a common-negative controller, where all the negative terminals of
PV array, battery and load can be grounded simultaneously or any one of them will be
Figure 2-2 Schematic of wiring diagram