Summary of Contents for Johnson Controls 100 Series
Page 1
FORM 100.50-EG12 (918) SERIES 100 SINGLE PACKAGE ROOFTOP UNITS ENGINEERING GUIDE 70–105 Tons Cooling and Heating (Gas, Electric, Water, and Steam) R-410A Mod G LD16707...
V : VAV, SZVAV 0 : 380 / 3 / 60 S : Side Return F : FlexSys ™ Y : Johnson Controls A : Std. Product, Simplicity Elite B : Bottom Supply B : Special Product, Simplicity Elite L : Left Supply X : Std.
Better Economy... Lower total cost of ownership • Johnson Controls provides a standard product offering that meets the latest ASHRAE 90.1 energy efficiency requirements. • Fully modulating gas heat and greater steps of capacity control offer superior off- design performance while maintaining optimum occupant comfort.
80–250 kW depending on the single package unit model size. The number of stages varies by size and voltage, but all have a minimum of two stages of capacity. Units with electric heat are ETL listed. JOHNSON CONTROLS...
Page 7
0.0°F through the use of suction and discharge pressure transducers on the circuit(s). Pressure Transducers with Readout Capability – This option includes suction and dis- charge pressure transducers on each circuit and provides pressure readout of all circuits at the unit control panel. JOHNSON CONTROLS...
Page 8
Barometric Relief – This option does not include an exhaust or return fan, but rather uses barometric relief dampers to exhaust air from the building. The dampers will open relative to the building pressure. The opening pressure is adjustable via a spring tension adjustment. JOHNSON CONTROLS...
Page 9
The supply fan can be optionally equipped with a piezo ring to precisely measure the amount of air delivered to the conditioned space. The speed of the supply fan is controlled by a VFD. JOHNSON CONTROLS...
Page 10
CONDENSER FEATURES AND OPTIONS Scroll Compressors – Reliable, efficient, trouble-free operation is the true measure of a single package unit’s value. That’s why Johnson Controls Series 100 Single package units use established scroll compressor technology to deliver dependable, economical performance in a wide range of applications. With the Series 100 Single package units, you get the latest generation of compressor enhancements added to the scroll’s inherent...
Page 11
Magnahelic Filter Pressure Gauge – On units equipped with downstream filtration, a magnahelic filter gauge is included and visible on the exterior of the unit. The filter gauge measures the air pressure drop for through the rigid filter bank to indicate when replace- ment is required. JOHNSON CONTROLS...
Page 12
FORM100.50-EG12 (918) Features and Benefits (Cont'd) YPAL070–105 MODEL JOHNSON CONTROLS...
Unit clearances are designed so that technicians have enough space between units, building walls, and edges of building to gain access safely. In cases where space is limited, please call your local Johnson Controls representative for addi- tional information.
Page 14
Erecting a fence around the unit is common practice. • Roof curb – Johnson Controls offers optional roof curbs designed specifically for the Series 100 footprint. These curbs come in full perimeter or open condenser models and are shipped disassembled and require field assembly and installation.
Page 15
HVAC equipment. If the application calls for horizontal supply and return air, Johnson Controls can ship it from the factory as a horizontal unit. This option eliminates the need for field modification of equipment saving time and money.
Page 16
FIGURE 2 - TRADITIONAL OVERHEAD VAV AIR DELIVERY SYSTEM For VAV applications, the Johnson Controls Series 100 unit uses a VFD to modulate fan speed and maintain a constant duct static pressure. VFDs offer superior control over the operation of the unit at part load, and offer the additional benefits of quieter and more ef- ficient operation when compared to IGV.
Page 17
Johnson Controls offers a powered return fan that is located in the return plenum. This fan operates coincidentally with the supply fan and draws return air back through the return ductwork and into a pressurized plenum.
Page 18
Control is accomplished via either a discharge damper or a VFD. Johnson Controls recommends the use of a VFD to reduce energy consumption, sound levels and improved reliability due to fewer moving parts.
Motor Size Range (min. to max. HP, total 10–30 10–30 10–30 10–40 10–40 for two fans) Airflow Range (min. to max. CFM) 4,000–32,000 4,000–32,000 4,000–32,000 4,000–36,000 4,000–36,000 Static Pressure Range (min. to max. iwg) 0–3 inches 0–3 inches 0–3 inches 0–3 inches 0–3 inches JOHNSON CONTROLS...
Page 20
FILTERS - 12-INCH RIGID 95% IN POST-FILTER POSITION (MERV 14) Quantity 2/7/9 2/7/9 2/7/9 7/12 7/12 16x20/25x16/ 16x20/25x16/ 16x20/25x16/ Size (length x width) (inch) 25x16/25x20 25x16/25x20 25x20 25x20 25x20 Total Filter Face Area (square feet) 55.1 55.1 55.1 61.1 61.1 JOHNSON CONTROLS...
2-inch throwaway filter. 2. Base weights shown represent approximate operating weights and have a ±10% accuracy. To calculate weight for a specific configura- tion, use YORKworks or contact a Johnson Controls sales representative. TABLE 6 - COMPONENT WEIGHTS (LBS)
Page 23
Rear OA Hood Tray & Liner OA Filters Back Top OA Filters Back Bottom OA Filters Right Top OA Filters Right Bottom OA Filters Left Top OA Filters Left Bottom POWER EXHAUST Exhaust Motor Base, 256 T Frame Exhaust Fan JOHNSON CONTROLS...
Page 24
1. The weight given is the total weight of all eight aluminum coils and all eight copper coils, respectively. Indicates that particular option is not available with that model size. 2. The 0–100% AMS option needs some predetermined minimum airflow rate to work. JOHNSON CONTROLS...
Minimum gas pressure is 4.5 iwg. ELECTRIC HEATING TABLE 13 - ELECTRIC HEAT PERFORMANCE DATA HEAT CAPACITY AIRFLOW MIN MAX TEMP RISE UNIT SIZE (KW) (MBH) (CFM) (°F) 10,000 12,000 70–80 TON 14,000 15,000 12,000 14,000 90–105 TON 15,000 16,000 JOHNSON CONTROLS...
34.0 40.3 47.2 34,000 30.9 38.2 44.8 NOTE: For performance at operating points not included in these tables, consult your local Johnson Controls representative. TABLE 15 - YPAL070–105: 32-INCH AIRFOIL FAN TOTAL STATIC PRESSURE (IWG) STD. AIR 18,000 12.8 1046 17.0...
Page 52
34.3 1,261 40.6 1,313 47.1 NOTE: For performance at operating points not included in these tables, consult your local Johnson Controls representative. TABLE 17 - YPAL070–105: DDP402-9-120 DIRECT DRIVE PLENUM (DDP) SUPPLY FAN TOTAL STATIC PRESSURE (IWG) STD. AIR 18,000 12.8...
1. Return air opening pressure drop does not include an exhaust fan. Use the value in the Powered Exhaust column to determine return air pressure drop attributed to the exhaust fan assembly. 2. Front return is not available with barometric relief, exhaust fans or return fans. 3. Pressure drop for rigid filter rack includes a 2-inch throwaway pre-filter. JOHNSON CONTROLS...
0.44 36,000 0.22 0.29 0.36 0.50 TABLE 21 - ELECTRIC HEATER SIZE AVAILABILITY BY UNIT SIZE MODEL 80kW 108kW 150kW* 200kW* 250kW* YPAL070–080 YPAL090–105** *150–250kW electric heat not available in 200-230V configurations. **For 208V YPAL105, contact Johnson Controls. JOHNSON CONTROLS...
13.6 24000 11.7 12.7 14.0 26000 14.7 NOTE: For performance at operating points not included in these tables, consult your local Johnson Controls representative. TABLE 23 - EXHAUST FAN PERFORMANCE FAN TYPE 18X18 20X18 YPAL070–080 YPAL090–105 TABLE 24 - DUAL 20 X 18 FORWARD-CURVED FAN TOTAL STATIC PRESSURE (IWG) 0.25...
1864 39.8 1912 36000 29.7 1813 33.3 1859 36.9 1902 NOTE: For performance at operating points not included in these tables, consult your local Johnson Controls representative. TABLE 26 - RETURN FAN PERFORMANCE FAN TYPE 2X270 YPAL070–080 YPAL090–105 JOHNSON CONTROLS...
CONTROL SEQUENCES (VAV & SZVAV) GENERAL The control system for the Johnson Controls Series 100 single package unit is fully self- contained and based around a single package unit controller. To aid in unit setup, mainte- nance, and operation, the single package unit controller is equipped with a user interface that is based around a 4 line x 20 character backlit LCD display.
Page 62
OAT is less than the ref- erence temperature setting. This method of economizing allows the reference temperature setting to be set higher than the dry bulb economizer and is consequently a more efficient single package unit economizer. JOHNSON CONTROLS...
Page 63
Because this type of exhaust is not powered, the amount of air exhausted will be limited to the static pressure that will need to be overcome. JOHNSON CONTROLS...
Page 64
With the optional low ambient controls, mechanical cooling is allowed down to outside air tem- peratures of 0.0°F. JOHNSON CONTROLS...
Page 65
RAT is equal to or less than the RAT heating setpoint minus 0.5°F, the unit controller will place the unit in the occupied heating mode. The unit will remain in the occupied heating mode until the RAT is equal to or greater than the RAT heating setpoint plus 0.5°F. JOHNSON CONTROLS...
Page 66
0.5°F, the unit controller will place the unit in the unoccupied heating mode. The unit will remain in the unoccupied heating mode until the zone temperature is equal to or greater than the unoccupied zone heating setpoint plus 0.5°F. LD20073 FIGURE 4 - OPERATIONAL MODE: VARIABLE AIR VOLUME (VAV) JOHNSON CONTROLS...
Page 67
In the hardwired mode the input is an analog input to the control. In the communicated mode the input is a serial input from a bas con- trol system. LD19888 FIGURE 5 - OPERATIONAL MODE: SINGLE ZONE VAV (SZVAV) JOHNSON CONTROLS...
Page 68
If conditions are suitable for economizing, the single package unit controller will modulate the outside air damper in addition to staging heating steps up and down to maintain the zone temperature setpoint. JOHNSON CONTROLS...
6. On units with an optional disconnect switch, the supplied disconnect switch is a “Disconnecting Means” as defined in the N.E.C. Section 100, and is intended for isolating the unit from the available power supply to perform maintenance and troubleshooting. This disconnect switch is not intended to be a Load Break Device. FIGURE 6 - SINGLE-POINT POWER SUPPLY WIRING JOHNSON CONTROLS...
Page 71
100, and is intended for isolating the unit from the available power supply to perform maintenance and troubleshooting. This disconnect switch is not intended to be a Load Break Device. FIGURE 7 - SINGLE-POINT POWER SUPPLY WIRING WITH NON-FUSED DISCONNECT JOHNSON CONTROLS...
Page 72
6. On units with an optional disconnect switch, the supplied disconnect switch is a “Disconnecting Means” as defined in the N.E.C. Section 100, and is intended for isolating the unit from the available power supply to perform maintenance and troubleshooting. This disconnect switch is not intended to be a Load Break Device. FIGURE 8 - DUAL-POINT POWER SUPPLY WIRING JOHNSON CONTROLS...
FORM 100.50-EG12 (918) General Arrangement Drawing – 70–80 Ton Models BOTTOM SUPPLY / BOTTOM RETURN FIGURE 11 - GENERAL ARRANGEMENT DRAWING LD08128 JOHNSON CONTROLS...
Page 76
FORM100.50-EG12 (918) General Arrangement Drawing – 70–80 Ton Models (Cont'd) LEFT SUPPLY / LEFT RETURN FIGURE 12 - GENERAL ARRANGEMENT DRAWING JOHNSON CONTROLS...
Page 77
FORM 100.50-EG12 (918) LEFT SUPPLY / FRONT RETURN FIGURE 13 - GENERAL ARRANGEMENT DRAWING LD08130 JOHNSON CONTROLS...
Page 78
FORM100.50-EG12 (918) General Arrangement Drawing – 70–80 Ton Models (Cont'd) EXTENDED CABINET / BOTTOM SUPPLY / BOTTOM RETURN FIGURE 14 - GENERAL ARRANGEMENT DRAWING JOHNSON CONTROLS...
Page 79
FORM 100.50-EG12 (918) EXTENDED CABINET / LEFT SUPPLY / LEFT RETURN FIGURE 15 - GENERAL ARRANGEMENT DRAWING ld08137 JOHNSON CONTROLS...
Page 80
FORM100.50-EG12 (918) General Arrangement Drawing – 70–80 Ton Models (Cont'd) EXTENDED CABINET / LEFT SUPPLY / FRONT RETURN FIGURE 16 - GENERAL ARRANGEMENT DRAWING JOHNSON CONTROLS...
FORM 100.50-EG12 (918) General Arrangement Drawing – 90–105 Ton Models BOTTOM SUPPLY / BOTTOM RETURN FIGURE 17 - GENERAL ARRANGEMENT DRAWING ld08131 JOHNSON CONTROLS...
Page 82
FORM100.50-EG12 (918) General Arrangement Drawing – 90–105 Ton Models (Cont'd) LEFT SUPPLY / LEFT RETURN FIGURE 18 - GENERAL ARRANGEMENT DRAWING JOHNSON CONTROLS...
Page 83
FORM 100.50-EG12 (918) LEFT SUPPLY / FRONT RETURN FIGURE 19 - GENERAL ARRANGEMENT DRAWING ld08133 JOHNSON CONTROLS...
Page 84
FORM100.50-EG12 (918) General Arrangement Drawing – 90–105 Ton Models (Cont'd) EXTENDED CABINET / BOTTOM SUPPLY / BOTTOM RETURN FIGURE 20 - GENERAL ARRANGEMENT DRAWING JOHNSON CONTROLS...
Page 85
FORM 100.50-EG12 (918) EXTENDED CABINET / LEFT SUPPLY / LEFT RETURN FIGURE 21 - GENERAL ARRANGEMENT DRAWING LD08137 JOHNSON CONTROLS...
Page 86
FORM100.50-EG12 (918) General Arrangement Drawing – 90–105 Ton Models (Cont'd) EXTENDED CABINET / LEFT SUPPLY / BOTTOM RETURN FIGURE 22 - GENERAL ARRANGEMENT DRAWING JOHNSON CONTROLS...
The cap design must be sloped away from the supply duct opening to the end of the unit for the drainage of the moisture off of the top of the cap. FIGURE 23 - GENERAL ARRANGEMENT DRAWING JOHNSON CONTROLS...
Page 88
2. Curb configuration for “bottom” return and “bottom” supply. 3. These drawings are not intended as construction documents for the field fabricated roof curbs. Johnson Controls will not be responsible for the unit fit up, leak integrity, or sound level for installation using field fabricated roof curbs.
FPT = Female Pipe Thread Hot Water Coil Connections w/ controls are valve connections facing bottom of the unit, at locations indicated. Steam and Hot Water connections w/o controls are fittings connections facing side of the unit, at locations indicated. JOHNSON CONTROLS...
1. Structural supports for units. 2. Roof curb transition. 3. Piping size and connection/header locations. 4. Electrical power requirements and wire/conduit and overcurrent protection sizes. 5. All costs incurred to modify the building provisions to accept the furnished units. JOHNSON CONTROLS...
Page 92
460V [208V/230V/575V] three-phase, 60Hz power supply, outdoor air handling section with return and supply openings, discharge plenum, direct-expansion refrigerant condensing section. JOHNSON CONTROLS...
Page 93
0–25% outside air shall be provided. The minimum position shall be manually adjustable from 0–25%. Control shall be based on the occupied mode of the unit. For occupied mode, the damper shall be open to the minimum position and for unoccupied, it shall be closed. JOHNSON CONTROLS...
Page 94
A discharge damper shall be provided to modulate building exhaust. The damper shall be controlled via building pressure. The return damper shall linked with the outside air damper to modulate volumes of return and outside airflows. JOHNSON CONTROLS...
Page 95
3/8-inch OD copper, with internally enhanced tubes. Fins shall be enhanced me- chanically expanded to bond with the copper tubes. Coil casing shall be fabricated from heavy gauge galvanized steel. All coils shall be pressure tested at a minimum of 450 psig. JOHNSON CONTROLS...
Page 96
Airflow measurement device shall be ca¬pable of measurement accuracy of +/-5%. Airflow measurement ring and trans¬ducer shall be supplied for integration into a field-supplied controller. f. Fan Inlet Screen: Unit shall be provided with a fan inlet screen. JOHNSON CONTROLS...
Page 97
3. Modulating Gas Heat: The heating section shall include an induced draft furnace in 8:1 modulation [16:1, 24:1] of heating capacity. Heat Exchanger(s): The heat exchanger(s) shall be constructed of tubular alumi- nized steel [stainless steel], with stainless steel flue baffles and flue assembly. JOHNSON CONTROLS...
Page 98
Freezestat shall be provided to prevent coil freeze-up. Testing: Completed coil, including headers, connections and return bends shall be tested with 325 pounds compressed air under water. Coils shall be designed for op- eration at 250 psig design working pressure. JOHNSON CONTROLS...
Page 99
All compressor-to-pipe connections shall be brazed to minimize potential for leaks. Each compressor shall include a replaceable suction screen, discharge line check valve, and oil sight glass. JOHNSON CONTROLS...
Page 100
In the event of a unit shutdown or alarm, the oper- ating conditions, date and time shall be stored in the shutdown history to facilitate service and troubleshooting. JOHNSON CONTROLS...
Page 101
Manufacturer instructions. Adjust and level the single package unit on support structure. INSPECTION AND START-UP SUPERVISION A factory-trained service representative of the manufacturer shall supervise the unit start- up and application specific calibration of control components. JOHNSON CONTROLS...
Need help?
Do you have a question about the 100 Series and is the answer not in the manual?
Questions and answers