Inverter-driven air conditioning units, outdoor units, indoor units duct, indoor units cassette, indoor units ceiling (93 pages)
Summary of Contents for Johnson Controls 100 Series
Page 1
PACKAGED ROOFTOP UNITS Supersedes 100.50-NOM6 (316) Form 100.50-NOM6 (817) INSTALLATION, OPERATION, MAINTENANCE 035-21979-004 SERIES 100 SINGLE PACKAGED UNITS YPAL DESIGN LEVEL F WITH SIMPLICITY ELITE CONTROL LD16707 50 THROUGH 65 TONS Issue Date: August 7, 2017...
Page 2
All wiring must be in accor- dance with Johnson Controls’ published specifications and must be performed only by a qualified electrician. Johnson Controls will NOT be responsible for damage/problems resulting from improper connections to the controls or application of improper control signals.
Page 3
FORM 100.50-NOM6 ISSUE DATE: 8/07/2017 CHANGEABILITY OF THIS DOCUMENT In complying with Johnson Controls’ policy for con- regarding the applicability of these documents, rig- tinuous product improvement, the information con- ging, lifting, and operating/service personnel should tained in this document is subject to change without verify whether the equipment has been modified and notice.
Page 4
G :Staged Natural Gas Heat SS HX B :Bottom Supply M :Full Modulating Gas Heat L :Left Supply F :Full Modulating Gas Heat SS Staged HX R :Right Supply E :Electric Heat H :Hot Water Heat S :Steam Heat LD13270A JOHNSON CONTROLS...
Page 5
Single Point Power ..........................15 Dual Point Power ...........................15 Unit-Mounted Disconnect ........................16 Service And Installation ..........................16 Access Doors ............................16 Service Valves ............................16 Convenience Outlet ..........................16 Factory Run-Tested ..........................16 Gas Heat Sections ..........................16 Replaceable Core Filter Drier Option ....................16 JOHNSON CONTROLS...
Static Pressure Control Plastic Tubing ....................46 Duct Static Transducer ..........................46 Building Pressure Transducer ....................... 46 Static Pressure Probe Installation ......................46 Duct System ..............................48 Duct Connection Guidelines ........................48 Sound and Vibration Transmission ......................... 48 Gas Heating ..............................49 Gas Piping .............................49 JOHNSON CONTROLS...
Page 7
Fan Shaft Bearings ..........................62 Bearing Lock Devices ..........................63 Eccentric Type ............................63 Torquing of Set-screws .........................65 SECTION 5 – SEQUENCE OF OPERATION ......................67 Unit Type ................................ 67 Occupied / Unoccupied Mode ........................67 Constant Volume Mode (CV) .......................... 67 JOHNSON CONTROLS...
Page 8
Excessive SAT (Supply Air Temperature) Control ..................84 Cooling ..............................84 Heating ..............................85 Space Sensor With Setpoint Adjustment ......................86 Sequence of Operation .........................86 Space Sensor Fault Override Enable ......................86 Sequence of Operation .........................87 Remote Control .............................. 87 Sequence of Operation .........................87 JOHNSON CONTROLS...
Page 9
Alarm History ..............................99 SECTION 6 – USER INTERFACE ........................101 Interface Methods ............................101 Unit Controller Interface ..........................101 Program Button ............................101 Test/Up Button .............................. 102 Address / Down Button ..........................102 Alarm / Change ............................102 JOHNSON CONTROLS...
High-efficiency motors are standard. Motors are avail- occupied loads. The YORK YPAL system has 2 cir- able in ODP or TEFC construction. cuits in the unit. LD13271 FIGURE 1 - PACKAGED ROOFTOP AIR CONDITIONING UNIT JOHNSON CONTROLS...
Page 14
Allow for application of the YORK YPAL unit in HEATING SECTION sound-sensitive applications such as theaters and downtown areas. Contact Johnson Controls for more Staged Gas Heat details on site-specific requirements. The YORK YPAL rooftop gas furnace is an induced- draft gas furnace designed for high efficiency and reli- ability.
Page 15
This enables insulation from conditioned airstream. the unit to be operated in an emergency condition while minimizing power consumption. JOHNSON CONTROLS...
Page 16
Replaceable Core Filter Drier Option plify the service and repair task. Provides a means to remove moisture, dirt and debris from the refrigeration circuit in the event it is opened. JOHNSON CONTROLS...
750,000 BTU Input - 385-01866-002 ment must be commissioned and serviced 1,125,000 BTU Input - 385-01866-003 by an authorized Johnson Controls service mechanic or a qualified service person Not suitable for use with conventional venting systems. experienced in packaged rooftop instal- lation.
In cases where space 6. Location of unit(s) should also be away from is limited, please call your local Johnson Controls rep- building flue stacks or exhaust ventilators to pre- resentative for additional information.
Typical rigging using proper spreader bars and cables loads. Contact your Johnson Controls Sales Office if is shown in Figure 4 on page 19. See Figure 3 on you have any questions regarding unit weights.
Supply Fan Motor - 15 HP Supply Fan Motor - 25 HP Supply Fan Motor - 30 HP Supply Fan Motor - 40 HP SUPPLY FAN VFD Supply Fan VFD - 5 - 10 HP Supply Fan VFD - 30 - 40 HP JOHNSON CONTROLS...
Page 21
Electric Heat - 150kW (Max) Electric Heat - 200kW (Max) Electric Heat - 250kW (Max) Gas Heat - 375 MBH (Max) Gas Heat - 750 MBH (Max) Gas Heat - 1125 MBH (Max) Hot Water Coil Steam Coil JOHNSON CONTROLS...
BASIC UNIT W/ ECONO and HEATING (Hot Water Heat) 2347 2143 2491 2728 2346 2148 2502 2732 BASIC UNIT W/ ECONO and HEATING (Hot Water Heat) and 2673 2441 2509 2748 2672 2446 2519 2752 POWER EXHAUST (10HP motor, modulating damper, no VFD) JOHNSON CONTROLS...
Page 23
BASIC UNIT W/ ECONO and HEATING (Hot Water Heat) 2588 2378 2675 2911 2587 2383 2686 2915 BASIC UNIT W/ ECONO and HEATING (Hot Water Heat) and 2916 2679 2690 2929 2915 2684 2701 2933 POWER EXHAUST (10HP motor, modulating damper, no VFD) JOHNSON CONTROLS...
BASIC UNIT W/ ECONO and HEATING (Hot Water Heat) 2588 2378 2675 2911 2587 2383 2686 2915 BASIC UNIT W/ ECONO and HEATING (hot Water Heat) and POWER EXHAUST (10HP motor, modulating 2916 2679 2690 2929 2915 2684 2701 2933 damper, no VFD) JOHNSON CONTROLS...
Johnson Controls will not be respon- sible for the unit fit up, leak integrity, or sound level Ground Level Locations with field fabricated roof curbs.
2. Curb configuration for “bottom” return and “bottom” supply. 3. These drawings are not intended as construction documents for the field fabricated roof curbs. Johnson Controls will not be responsible for the unit fit up, leak integrity, or sound level for installation using field fabricated roof curbs.
6 on page 26. The unit should never be operated for DRAIN PAN any length of time without the proper filters installed NO. 3 - FAN RUNNING AND CONDENSATE in the unit. LD13269 FIGURE 11 - DRAIN TRAP SHOWING WATER LOCATION DURING DRAW THROUGH OPERATION STAGES JOHNSON CONTROLS...
W2, and W3. The four thermostat cooling inputs con- nect to the P2 and P3 terminal block on the Simplicity The trap and drain lines should be protected from control board to terminals Y1, Y2, Y3, and Y4. freezing. Plumbing must conform to local codes. Use JOHNSON CONTROLS...
• On VAV units set the supply fan output to 100% supply an external power supply for the sensor. This is in addition to the two wires connect to the unit. The • Turn the power exhaust fan ON JOHNSON CONTROLS...
• At 2.0VDC – the control uses the lower setpoint • Between 2.0 VDC and 10VDC the change in setpoint is proportional to the change in voltage. • At 10.0VDC – the control uses the upper setpoint JOHNSON CONTROLS...
1. Wiring shown indicates typical wiring. Refer to the IOM manual for more detailed wiring methods and options. 2. All wiring is Class 2, low voltage. 3. Maximum power available from the 24 VAC terminal is 40 VA. 4. Use shielded wire where shown. FIGURE 13 - WIRING CONNECTIONS JOHNSON CONTROLS...
100% of the rated load amps for all other loads includ- ed in the circuit, per N.E.C. Article 440-34. The minimum recommended disconnect switch is based on 115% of the rated load amps for all loads in- cluded in the circuit, per N.E.C. JOHNSON CONTROLS...
3. Minimum Circuit Ampacity (MCA) is based on U.L. Standard 1995, Section 36.14 (N.E.C. Section 440-34). 4. Maximum Dual Element Fuse size is based on U.L. Standard 1995, Section 36.15 (N.E.C. Section 440-22). 5. Use copper conductors only. FIGURE 14 - SINGLE-POINT POWER SUPPLY WIRING JOHNSON CONTROLS...
100, and is intended for isolating the unit from the available power supply to perform maintenance and troubleshooting. This disconnect switch is not intended to be a Load Break Device. FIGURE 15 - SINGLE-POINT POWER SUPPLY WIRING WITH NON-FUSED DISCONNECT JOHNSON CONTROLS...
3. Minimum Circuit Ampacity (MCA) is based on U.L. Standard 1995, Section 36.14 (N.E.C. Section 440.34). 4. Maximum Dual Element Fuse size is based on U.L. Standard 1995, Section 36.15 (N.E.C. Section 440.22). 5. Use copper conductors only. FIGURE 16 - DUAL-POINT POWER SUPPLY WIRING JOHNSON CONTROLS...
Filter Compartment Compartment Economizer Economizer Compartment Compartment LD13127 The atmospheric probe should be mounted on the support post on the control side of the unit between the Economizer and the Filter compartment. FIGURE 17 - ATMOSPHERIC SENSOR PROBE JOHNSON CONTROLS...
This diagram is provided as a visual reference of the York YPAL discharge and return air openings and locations for all sizes. Please refer to Figures 5 through 10 for exact size and location of panels and openings. FIGURE 18 - DISCHARGE AND RETURN AIR OPENINGS JOHNSON CONTROLS...
2. LD11766 4. See Figure 20 on page 50 for the proper ori- FIGURE 20 - COMBUSTION VENT entation of the combustion vent. The internal baffle(s) must direct the flue gases upward. JOHNSON CONTROLS...
To protect warranty, this equipment must CHECKING THE SYSTEM PRIOR TO INITIAL be installed and serviced by an authorized START (NO POWER) Johnson Controls service mechanic or a Unit Checks qualified service person experienced in air handling and condenser unit instal- 1.
4. Insure proper compressor rotation - see following instruction on Verifying Compressor Rotation. Fan Hold Down EXHAUST FAN ASSEMBLY Brackets (4) Fan Hold Down Brackets (4) LD13268 SUPPLY FAN ASSEMBLY FIGURE 21 - FAN HOLD DOWN BRACKETS JOHNSON CONTROLS...
Pressure as shown in Table 22 on page 55. capable of sensing refrigerant R-410A. If the unit is functioning satisfactorily during the initial operating period, no safeties trip and the unit controls are functioning properly, the rooftop unit is ready to be placed into operation. JOHNSON CONTROLS...
NATURAL 4.5 “WC 13.5 “WC 1.2 “WC 3.5 “WC valve. On staged gas heat, as soon as the limit closes PROPANE 11.0 “WC 13.5 “WC 4.2 “WC 10.0”WC the ignition control will reinitiate the ignition sequence. JOHNSON CONTROLS...
23 on page 56. TABLE 24 - GAS HEAT PERFORMANCE DATA AIRFLOW GAS INPUT CAPACITY MAXIMUM OUTPUT CAPACITY TEMP. RISE UNIT (BTU/HR X 1000) (BTU/HR X 1000) (°F) MIN. MAX. 7,500 24,000 50-61 14,000 24,000 1125 21,000 24,000 JOHNSON CONTROLS...
Page 58
FORM 100.50-NOM6 SECTION 3 – START-UP ISSUE DATE: 8/07/2017 THIS PAGE INTENTIONALLY LEFT BLANK. JOHNSON CONTROLS...
If a system failure compressor. occurs due to improper maintenance during the warran- ty period, Johnson Controls will not be liable for costs Fan Bearing Lubrication incurred to return the unit to satisfactory operation.
A belt ten- for proper operation. sioned too tightly can overload the motor electrical, causing nuisance tripping of the motor overloads and/ or motor failure and/or shaft failure. JOHNSON CONTROLS...
A Browning Belt tension gauge is used in Figure 25 on page 61 to properly tension belts. LD06355 LD06354 FIGURE 26 - EXAMPLE OF FC FAN SHAFT/WHEEL FIGURE 25 - BELT TENSIONING GAUGE MARKING JOHNSON CONTROLS...
If an adapter or grease fitting of improper size and length is used, the locking pin may be either too tight or loose and can affect the alignment and re-lubrication of the bearing. JOHNSON CONTROLS...
It is extremely important to ensure that proper radial clearances are observed between the roller bearings and outer face. Failure to make proper adjustments will cause prema- ture failure of the bearing. 00536vip Seal FIGURE 30 - SPLIT BEARING JOHNSON CONTROLS...
Page 66
FORM 100.50-NOM6 SECTION 4 – MAINTENANCE ISSUE DATE: 8/07/2017 THIS PAGE INTENTIONALLY LEFT BLANK. JOHNSON CONTROLS...
SYSTEMS OPTIONS tab in the Simplicity PC • “COOLING MODE OPERATION ENABLED” software package. – must be enabled using Parameter 53 under the PROGRAM key on the Simplicity control board or under the COOLING SETUP tab in the Sim- plicity PC software package. JOHNSON CONTROLS...
A programmable thermostat would be required in order • Y1 – First Stage of Cooling – 1st compressor from to change the heating temperature settings between oc- System 1. cupied and unoccupied. • Y2 – Second Stage of Cooling – 2nd compressor from System 1. JOHNSON CONTROLS...
COOLING SETUP tab of the in the – If the space temperature is greater than 2.0° F Simplicity PC software package. or more above the “CV OCCUPIED COOLING SETPOINT” or “CV UNOCCUPIED COOLING SETPOINT” the control will bring on the first JOHNSON CONTROLS...
• If after 3 or 5 minutes the return air temperature is • “CV OCCUPIED HEATING SETPOINT” – using between 1.5° F and 1.9° F above the “CV OCCU- Parameter 11 under the PROGRAM key on the JOHNSON CONTROLS...
“CV OCCUPIED HEATING” or “CV PROGRAM key on the Simplicity control board UNOCCUPIED HEATING SETPOINT” the con- or under the COOLING SETUP tab in the Sim- trol energizes the first stage of heat. plicity PC software package. JOHNSON CONTROLS...
• “VAV COOLING SUPPLY AIR TEMP UPPER SAT SETPOINT” or “VAV COOLING SUPPLY SETPOINT” – using Parameter 23 under the AIR TEMP LOWER SETPOINT”. If turning a PROGRAM key on the Simplicity control board compressor ON would result in the specified drop JOHNSON CONTROLS...
Simplicity control board or under the HEAT- The supply air temperature is still 5.0° F or ING SETUP tab in the Simplicity PC software more, greater than the “VAV UPPER COOLING package. SAT SETPOINT” or “VAV LOWER COOLING SAT SETPOINT”. JOHNSON CONTROLS...
ON. the Simplicity PC software package. • The same logic will be used to stage ON compres- The Simplicity Control will control the operation of sor 3 and 4. the compressors as follows: JOHNSON CONTROLS...
A call for the third stage of compressor operation will “MORNING WARM UP / VAV RETURN AIR close an output at CF2, terminal 2 of the P13 connec- TEMP SETPOINT”. tor. The 24VAC output will energize the 8M contactor and turn on condenser fan 3. JOHNSON CONTROLS...
The VFD controls the speed of the fan based on a dis- 350 PSIG 80 PSIG charge pressure setpoint and a differential range. When 6 O’CLOCK 6 O’CLOCK discharge pressure reaches approximately 270 PSIG, the VFD will start the fan if the Unit Controller is call- JOHNSON CONTROLS...
“APS” connections at the P11 connector on the Sim- til the control receives a signal that the gas valve plicity control board. If this input does not go to the is energized. high state in this time frame the Simplicity Control will JOHNSON CONTROLS...
SETPOINT” by varying the speed of the supply fan. As have timed out. The “HEAT, FAN OFF DELAY” the duct static pressure goes up the speed goes down. timer does not start until the control receives a sig- nal that the gas valve is de-energized. JOHNSON CONTROLS...
1.0 • The outside air temperature is less than or equal to BTU/LB below the “ECONOMIZER OUTSIDE the “ECONOMIZER OUTSIDE AIR TEMP EN- AIR ENTHALPY SETPOINT”. ABLE SETPOINT”. • The Simplicity Control has a demand for cooling operation. JOHNSON CONTROLS...
Simplicity PC software package. • “ECONOMIZER INSTALLED” - must be dis- abled using Parameter 32 under the PROGRAM key on the Simplicity Control board or under the ECONOMIZER/EXHAUST tab in the Simplicity PC software package. JOHNSON CONTROLS...
3-minutes until all the compressor have been turned off. • When the space temperature is equal to or greater than 2.0° F above the “VAV SUPPLY AIR TEMP RESET SETPOINT” the Simplicity Control will use the “VAV COOLING SUPPLY AIR TEMP LOWER SETPOINT”. JOHNSON CONTROLS...
• The unit must be in an occupied or unoccupied SETPOINT” or “VAV COOLING SUPPLY AIR cooling mode. TEMP LOWER SETPOINT” the Simplicity Con- trol will turn off the compressor close the econo- mizer damper to its minimum position. JOHNSON CONTROLS...
TURN OFF WITHIN BELOW OPEN TURN OFF WITHIN WITHIN TURN OFF * If the economizer damper opens to 100%, the compressor will turn off and the economizer damper will remain at 100%. The following parameters must be programmed: JOHNSON CONTROLS...
• ECON OPERATION – Economizer damper will under the PROGRAM key on the Simplicity con- open to BRING SAT into the SAT COMFORT trol board or under the COOLING SETUP tab in ZONE. the Simplicity PC software package. JOHNSON CONTROLS...
0.1° F or more above this • The Simplicity Control starts a 10 minute and 3 value and the heat stage minimum run time has minute timing sequence. been met the Simplicity Control will turn off the heat stage. JOHNSON CONTROLS...
• If after 10 minutes the supply air temperature is TEMS OPTIONS tab of the Simplicity software pack- still greater than the “SUPPLY AIR TEMP LIMIT age. HEATING SETPOINT” minus 10.1° F the Sim- plicity Control will keep the heat stage(s) off un- JOHNSON CONTROLS...
• The hard wired input is connected to the Simplici- will be turned back ON with a 30 second delay be- ty Elite control board at the “REM+” and “REM- tween compressors. “ terminals of the P19 connector. JOHNSON CONTROLS...
“INTELLI-START OPERATION ENABLE” must be programmed in order to use this feature under the SYS- • Cooling operation TEMS OPTIONS tab of the Simplicity PC software package. JOHNSON CONTROLS...
HEATING SETUP tab – If the current outdoor air temperature is 10.0° of the Simplicity PC software package. F or more above the previous day the Simplic- JOHNSON CONTROLS...
F of the economize to the minimum position. the “HYDRONIC HEATING STAGE #2 SUPPLYAIR • Heating operation will continue until the return SETPOINT”. air temperature is equal to or above the “MORN- ING WARM UP/VAV RETURN AIR TEMP SETPOINT”. JOHNSON CONTROLS...
PI logic which could move the dampers beyond • Fixed Minimum – Economizer option required. the “ECONOMIZER MINIMUM POSITION”; however, the Economizer PI logic can never close • Demand Ventilation – Economizer option re- the dampers less than the “ECONOMIZER MINI- quired. MUM POSITION”. JOHNSON CONTROLS...
“MAXIMUM IAQ ECONOMIZER POSI- TION” based on the following: • The Simplicity Elite control will try to maintain the CO level in the conditioned space to plus or minus 100 PPM of the “IAQ SETPOINT”. JOHNSON CONTROLS...
EXHAUST FAN TO TURN OFF” – must be pro- less than the “ECONOMIZER MINIMUM POSITION” grammed using Parameter 49 under the PRO- parameter. GRAM key on the Simplicity Elite control board or under the ECONOMIZER/EXHAUST tab in the Simplicity PC software package. JOHNSON CONTROLS...
When the building static pressure is 0.015" WC or more below the “BUILDING PRESSURE SETPOINT” the Simplicity Elite control opens the output to the exhaust fan motor. The minimum run time is 10 seconds and the minimum off time is 60 seconds. JOHNSON CONTROLS...
• “BUILDING PRESSURE SETPOINT” must be TEM OPTIONS tab in the Simplicity PC software package. programmed using Parameter 31 under the PRO- GRAM key on the Simplicity Elite control board or under the ECONOMIZER/EXHAUST tab in the Simplicity PC software package. JOHNSON CONTROLS...
7M - contactor, energizes the hot gas cupied mode the following parameter must be en- bypass valve whenever the contactor is energized. The abled. hot gas valve monitors the suction pressure and will modulate to keep the suction pressure above 55 PSIG. JOHNSON CONTROLS...
120.0° F in 1.0° F increments. Temperature Alarm will be initiated. The range is 1 to 120 minutes in 1 minute increments. • The unit must have been in a given operating mode for 10 minutes before trending will begin. JOHNSON CONTROLS...
The Simplicity Elite control • The supply air temperature is 20 degrees above will declare an “ECONOMIZER MINIMUM the “SUPPLY AIR TEMP ALARM SETPOINT POSITION” Alarm and flash an Alarm Code FOR COOLING” setpoint for 10 minutes. JOHNSON CONTROLS...
3. After the cooling cycle is completed, the Simplic- ity Elite control sets the outdoor damper to its minimum position. 4. In order to reset the above alarms power to the unit must be cycled ON and OFF. JOHNSON CONTROLS...
Page 100
FORM 100.50-NOM6 SECTION 5 – SEQUENCE OF OPERATION ISSUE DATE: 8/07/2017 THIS PAGE INTENTIONALLY LEFT BLANK. JOHNSON CONTROLS...
Three of the buttons have multiple functions. The button functions are discussed in detail below. PROGRAM TEST/UP 2 CHARACTER DISPLAY RS 485 PORT 4 CHARACTER DISPLAY RS 485 PORT ADDRESS/DOWN LD13013 ALARM/CHANGE FIGURE 32 - UNIT CONTROLLER INTERFACE JOHNSON CONTROLS...
Table 33 on page 103. the first vacant communications address and changes its address to that address. It will then display the ad- dress on the display for two seconds. The controller is then connected to the network. JOHNSON CONTROLS...
0 - 5000 PPM 1000 Power Exhaust Installed Parameter Bit 0 = OFF, 1 = ON Modulating Power Exhaust Installed Parameter Bit 0 = OFF, 1 = ON Exhaust Vfd Installed Parameter Bit 0 = OFF, 1 = ON JOHNSON CONTROLS...
Page 104
0 = OFF, 1 = ON Erv Installed Parameter Bit 0 = OFF, 1 = ON Erv Unoccupied Fan Enable Parameter Bit 0 = OFF, 1 = ON Duct Static Shutdown Setpoint Pressure - Inches of H2O 0.000 - 5.000 4.500 JOHNSON CONTROLS...
PC or Personal Computer with “Simplicity PC” soft- ware installed. “Simplicity PC” software is available through the York web site. The instructions for down- loading the software are as follows: Simplicity PC Download 1. On the internet connect to York.Com. 2. Left click on software. JOHNSON CONTROLS...
Page 106
FORM 100.50-NOM6 SECTION 6 – USER INTERFACE ISSUE DATE: 8/07/2017 3. Left click on download to download the software and instruction manual. JOHNSON CONTROLS...
The actual name of the device will depend upon what it was named when it was set up. JOHNSON CONTROLS...
Page 108
FORM 100.50-NOM6 SECTION 6 – USER INTERFACE ISSUE DATE: 8/07/2017 LD13040 2. Left click on Add button 3a. Select Serial/USB direct connection 3b. Select proper Port Number LD13041 4. Click Add button JOHNSON CONTROLS...
Page 109
LD13040 7. Left click on desired Simplicity 6. Left click to expand tree Device. 7. Left-click on the particular Simplicity device de- sired. JOHNSON CONTROLS...
Page 110
8. The right hand side of the screen fills with a series of tabs. The tabs allow you to access, read, and change settings for that device. Click on the tab that corresponds to the information you wish to access. LD13043 JOHNSON CONTROLS...
SECTION 6 – USER INTERFACE ISSUE DATE: 8/07/2017 Simplicity PC Data Screens The following pages identify the data contained in each of the tabs. Move the cursor to the tab and left click to open. DEVICE NAMES LD13015 EQUIPMENT INSTALLATION LD13016 JOHNSON CONTROLS...
If all the times are programmed to 12:00 AM, SCHEDULE SETTINGS tab. The weekly schedule the unit will operate 24 hours a day, 7 days a week. has two Occupied/Unoccupied times for each of the WEEKLY SCHEDULE SETTINGS LD13029 JOHNSON CONTROLS...
Click on the down arrow key to set the start date, the current month and year calendar will appear. Use the cursor to select HOLIDAY SCHEDULE LD13030 JOHNSON CONTROLS...
SECTION 6 – USER INTERFACE ISSUE DATE: 8/07/2017 Revising Settings To change a setpoint move the cursor to the value you want to change and left click and highlight the item. Left click to highlight Double click to open change screen LD13032 JOHNSON CONTROLS...
Page 127
To open the change screen double left click. The screen will show the current value and the accept- able range. Us the numeric key pad to enter the revised setting. Left click on “Update” and the value will be change at the Unit Controller. LD13033 JOHNSON CONTROLS...
Page 128
SECTION 6 – USER INTERFACE ISSUE DATE: 8/07/2017 To change a value move the cursor to the value you want to change and left click and highlight the item. Left click to highlight Double click to open change screen LD13034 JOHNSON CONTROLS...
Page 129
The screen will show the current value and option. Move the cursor and left click on the option you want to turn on. Left click on “Update” and the value will be change at the Unit Controller. LD13035 JOHNSON CONTROLS...
Input Status Byte #1 1 = Y1 On (Cooling 1st Stage) 1 = Y2 On (Cooling 2nd Stage) 1 = Y3 On (Cooling 3rd Stage) 1 = Y4 On (Cooling 4th Stage) 1 = W1 On (Heating 1st Stage) JOHNSON CONTROLS...
Page 131
1 = VAV; 0 = CV 1 = CV / VAV Out Of Range (Fault Condition) 1 = Low 24VAC Supply Voltage 17 H 23 L Input Status BYTE #6 1 = Program Button Pressed 1 = Test / Up Button Pressed JOHNSON CONTROLS...
Page 132
1 = Compressor #1 Off Because Of ASCD 1 = Compressor #2 Off Because Of ASCD 1 = Compressor #3 Off Because Of ASCD 1 = Compressor #4 Off Because Of ASCD 1A H 26 H Option BYTE #2 JOHNSON CONTROLS...
Page 133
1C H 28 H Alarm 1 - Most Recent Alarm. 1C L 28 L Alarm 2 1D H 29 H Alarm 3 1D L 29 L Alarm 4 1E H 30 H Alarm 5 – Oldest Stored Alarm. JOHNSON CONTROLS...
Page 134
68 H Real Time Clock Year Value 44 L 68 L Real Time Clock Month Value 45 H 69 H Real Time Clock Day Of Month Value 45 L 69 L Real Time Clock Day Of Week Value JOHNSON CONTROLS...
Page 135
Holiday #6 (Same Format As Holiday #1) 118 L 119 H - 77 H - 79 L Holiday #7 (Same Format As Holiday #1) 121 L 7A H - 7C 122 H - Holiday #8 (Same Format As Holiday #1) 124 L JOHNSON CONTROLS...
Page 136
166 L Return Air Humidity (%) A7 L 167 L Outside Air Humidity (%) A8 H 168 H Demand Ventilation (IAQ) Value (PPM Value, High BYTE) A8 L 168 L Demand Ventilation (IAQ) Value (PPM Value, Low BYTE) JOHNSON CONTROLS...
Page 137
Economizer Second Stage (Lower) Setpoint (Degrees F) B8 H 184 H Economizer Minimum Position (Percent) B9 H 185 H Economizer Outside Air Enthalpy Setpoint (BTU Per Pound) B9 L 185 L Economizer Return Air Enthalpy Setpoint (BTU Per Pound) JOHNSON CONTROLS...
Page 138
Compressor #3 Minimum Run Timer High BYTE (Seconds, C9 H 201 H Counts Down) Compressor #3 Minimum Run Timer Low BYTE (Seconds, C9 L 201 L Counts Down) Compressor #4 Minimum Run Timer High BYTE (Seconds, CA H 202 H Counts Down) JOHNSON CONTROLS...
Page 139
Outside Air Enthalpy (BTUS Per Pound) DC L 220 L Return Air Enthalpy (BTUS Per Pound) Maximum Demand Ventilation Economizer Position DE L 222 L (Percent Open) DF H 223 H Space Sensor Offset (0 = -5° F, 10 = +5° F) JOHNSON CONTROLS...
Page 140
E2 H 226 H Down) Heating Stage #3 Minimum Run Timer (Seconds, Counts E2 L 226 L Down) E3 H 227 H Low Ambient Economizer Minimum Position (Percent) E3 L 227 L Low Ambient Economizer Setpoint (Degrees F) JOHNSON CONTROLS...
This is used to determine the status of the off cycle timer. ON means COMP 3 ASCD ACTIVE the compressor 3 is in this mode This gives the actual time of the off cycle timer for compressor 3 in COMP 3 ASCD TIMER seconds. JOHNSON CONTROLS...
Page 142
This is the status of the binary input to terminal Y4 - fourth stage COOL 4 (Y4) cooling CURRENT BUS ADDRESS This identifies the address of the unit on the network This parameter identifies the cooling setpoint the Unit Controller is CV CURRENT OPERATING COOLING SETPOINT controlling to cooling too JOHNSON CONTROLS...
Page 143
This is the outdoor enthalpy setting which determines when to switch ECONOMIZER OUTSIDE AIR ENTHALPY into and out of economizer operation in single enthalpy economizer SETPOINT mode JOHNSON CONTROLS...
Page 144
This gives the actual time of the minimum run time timer for heat HEAT 2 MIN RUN TIMER section 2 in seconds This is the status of the binary input to terminal W3 - third stage HEAT 3 (W3) heating JOHNSON CONTROLS...
Page 145
HYDRONIC HEATING STAGE #2 SUPPLY AIR heating operation during second stage operation and also the control SETPOINT setpoint for VAV hydronic heating operation This parameter identifies to the Unit Controller the range of the CO IAQ SENSOR RANGE sensor in PPM JOHNSON CONTROLS...
Page 146
This allows compressor operation below 45.0° This is the status of the binary input from the low pressure switch for LPS1 compressor system 1 to the Unit Controller. ON - okay, OFF - faulted. JOHNSON CONTROLS...
Page 147
This parameter must be turned On to enable power exhaust operation This parameter is used to turn ON the Pre-occupancy Purge option. PRE-OCCUPANCY PURGE ENABLE This feature turns on the supply fan and opens the outdoor air damper prior to going into the occupied mode. JOHNSON CONTROLS...
Page 148
ON when TEMPERATURE this state is active STATUS COMPRESSOR OFF - ECON IS USING This identifies the compressors are off because the Unit Controller is FREE COOLING using outdoor air for cooling. ON when this is active JOHNSON CONTROLS...
Page 149
VAV COOLING SUPPLY AIR UPPER or LOWER SETPOINT This parameter is used to enter the current year 0 to 99. For example YEAR 7 would be 2007 JOHNSON CONTROLS...
Page 150
FORM 100.50-NOM6 SECTION 7 – PARAMETER DESCRIPTIONS AND OPTIONS ISSUE DATE: 8/07/2017 THIS PAGE INTENTIONALLY LEFT BLANK. JOHNSON CONTROLS...
Since both of the inputs will now be exposed to the same pressure, the differential pressure will be zero, and the output 2.5 VDC according to Table 40 on page 153. JOHNSON CONTROLS...
0 to 5VDC. Table 41 on page 0.00 2.50 154 illustrates the DC volt output from the transducer 0.20 3.00 for a given suction pressure. 0.40 3.50 0.60 4.00 0.80 4.50 1.00 5.00 JOHNSON CONTROLS...
TABLE 42 - FURNACE STATUS INPUT STAGED GAS HEAT MIN VOLTS DC MAX VOLTS DC FURNACE 1 STATUS FURNACE 2 STATUS FURNACE 3 STATUS 0.086 0.166 0.224 0.313 0.361 0.461 0.499 0.609 0.637 0.756 0.774 0.904 0.912 1.051 1.050 1.199 JOHNSON CONTROLS...
24VAC TO COMMON JUMP / COMPRESSOR 2A MOTOR PROTECTION CIRCUIT JUMP / 24VAC TO COMMON JUMP / COMPRESSOR 2B MOTOR PROTECTION CIRCUIT JUMP / 24VAC TO COMMON HEAT SECTION 1 GAS VALVE INPUT HEAT SECTION 2 GAS VALVE INPUT JOHNSON CONTROLS...
Page 157
24VAC TO COMMON COMPRESSOR SYSTEM 2 LOW PRESSURE LSP3 INPUT LPS4 NOT USED LPS4 JUMPERED TO LSP3 TERMINAL 24VAC INPUT TO UNIT CONTROLLER JUMPER TERMINAL INPUT FOR SMOKE SHUTDOWN JUMPER TERMINAL 24VAC TO COMMON COMPRESSOR 1A OUTPUT COMPRESSOR 1BOUTPUT JOHNSON CONTROLS...
Page 158
4TH STAGE COOLING INPUT FIELD OUTPUT IDENTIFIES UNIT IS IN THE HEATING MODE TERMINAL VAV OPEN - / AO (24VDC -) FIELD OUTPUT IDENTIFIES UNIT IS IN THE HEATING MODE TERMINAL VAV OPEN + / AO (24VDC +) JOHNSON CONTROLS...
Compressor System 2A Locked Out On Compressor Motor Protection Module. The Circuit Opened Three Times Within A 1-Hour Window. Compressor System 2B Locked Out On Compressor Motor Protection Module. The Circuit Opened Three Times Within A 1-Hour Window. JOHNSON CONTROLS...
Page 160
The Space Temperature Setpoint. This Indicates The Duct Static Has Not Risen Quickly Enough In A Vav Unit When The Supply Fan Is Energized. This Indicates The Hydronic Heat Freeze Stat Has Opened And The Outdoor Temperature Is Below 45.0° F. JOHNSON CONTROLS...
C40 of the P12 connector. The binary input back to the pressors for that system will be turned off. If the high Unit Controller from the compressor protection mod- pressure switch for system 1, (compressors 1A, 1B), ule is wire 444 at terminal C40 of the P12 connector. JOHNSON CONTROLS...
Page 162
P10 connector. The limit input for heat section shoot compare the resistance of the input to the actual 3 is located at terminal LIM3 wire 533 of the P10 con- outdoor air temperature using Table 37 on page 152. nector. JOHNSON CONTROLS...
Page 163
Clock is not functioning. The Unit Controller will shut ler is shut down. Try recycling power to the control. If down all operation. Try recycling power to the control. the fault reappears replace the Unit Controller. If the fault reappears replace the Unit Controller. JOHNSON CONTROLS...
Page 164
This alarm indicates the duct static pressure has ex- 20%. ceeded the Duct Static Shutdown Setpoint. The prob- lem could be caused by a faulty Duct Static Pressure Transducer input. To check measure the VDC input between terminal DP+ wire 337 at the P21 connector JOHNSON CONTROLS...
Page 165
10 minutes. terminal FSI, wire 388. • The temperature is below or above the space tem- perature setpoint and the trend continues to be away from the space temperature setpoint and the “SPACE TEMP TRENDING ALARM TIME” has expired. JOHNSON CONTROLS...
Need help?
Do you have a question about the 100 Series and is the answer not in the manual?
Questions and answers