Crankcase Heaters
Explains the function of crankcase heaters to prevent refrigerant migration.
Initial Start‑Up
Procedure after pre-checks are completed and control panel programmed.
Leak Checking
Instructions for leak checking compressors, fittings, and piping.
Gas Heat Models
Covers pre-start and post-start checks for gas heat operations.
General
Emphasizes the importance of a planned maintenance program.
Sheave Alignment
Explains checking and correcting sheave alignment to prevent failure.
Belts
Guidance on checking and replacing belts as a set.
Belt Tensioning
Instructions for adjusting belt tension using fan skid data plate information.
UNIT TYPE
Explains configuring the control for Constant Volume or Variable Air Volume operation.
Thermostat Input
Describes receiving cooling/heating inputs from the thermostat.
Condenser Fan Operation
Details the sequence for condenser fan operation based on compressor stages and discharge pressure.
Economizer
Covers economizer control methods: Dry Bulb, Single Enthalpy, Dual Enthalpy.
Comfort Ventilation
Uses economizer to control supply air temp, energizing cooling/heating if needed.
REMOTE CONTROL
Allows VAV unit setpoint variation via a hardwired 0-10VDC signal.
REDLINE
Temporarily reduces electrical consumption by reducing compressor stages.
LOADSHED
Temporarily reduces electrical consumption by turning off active compressors.
DIRTY FILTER
Initiates an alarm when filter pressure drop exceeds switch setting.
INTELLI-START
Energizes heating/cooling to bring space temp to setpoints before occupancy.
Subsequent Operation
Determines pre-start time for heating/cooling based on previous day's performance.
MORNING WARM UP
Energizes heating section to bring space temperature to conditions before occupancy.
HYDRONIC HEAT
Parameters and sequence for hydronic heating operation.
VENTILATION
Options for ventilation control: Manual, Fixed Minimum, Demand Ventilation.
Demand Ventilation
Modulates outdoor damper to maintain CO2 levels within setpoint +/- 100 PPM.
Pre-Occupancy Purge
Purges air by running blower and opening economizer during unoccupied period.
Hot Gas Bypass
Injects discharge gas to artificially load evaporator coil under light load.
Alarm History
Allows viewing the last five alarms stored in the Simplicity Elite control.
Interface Methods
Explains three methods for interfacing with the Simplicity Elite control.
Fans
Displays parameters related to fan operation, delays, and setpoints.
Cooling Setup
Contains parameters for cooling mode, setpoints, and limits.
Cooling Status
Displays current status of compressors, economizer, and fan delays.
Heating Setup
Contains parameters for heating mode, setpoints, and limits.
Heating Status
Displays current status of heating outputs and controls.
System Options
Lists various system options and their programmed values.
Outputs/Status
Displays current status of unit outputs like fans, compressors, and heating.
Inputs
Shows the status of various unit inputs like sensors and switches.
Graphic
Visual representation of unit status with sensor readings.
Clock
Interface for updating the unit's clock.
ALARMS
Displays active and historical alarm information.
Revising Settings
How to change parameter values using the unit controller interface.
CO2 Sensor
Describes CO2 sensor usage for Demand Ventilation and its output.
Need help?
Do you have a question about the 105 and is the answer not in the manual?
Questions and answers