14 1769-L32E, 1769-L35E CompactLogix Controller
6. Attach the modules to the panel by using the mounting
screws.
If you are mounting more modules, mount only the last one of this group and put the
TIP
others aside. This reduces remounting time when you are drilling and tapping the next
group of modules.
7. Repeat steps 1...6 for any remaining modules.

DIN Rail Mounting

The controller can be mounted on the following DIN rails:
• EN 50 022 - 35 x 7.5 mm (1.38 x 0.30 in.)
• EN 50 022 - 35 x 15 mm (1.38 x 0.59 in.)
This product is grounded through the DIN rail to chassis ground. Use zinc plated
ATTENTION
yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail
materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor
conductors, can result in improper or intermittent grounding. Secure DIN rail to mounting
surface approximately every 200 mm (7.8 in.) and use end-anchors appropriately.
1. Before mounting the controller on a DIN rail, close the DIN
rail latches.
2. Press the DIN rail mounting area of the controller against the
DIN rail.
The latches will momentarily open and lock into place.