Commissioning

6.8 Application example

6.8
Application example
6.8.1

Level application example

The application is a vessel that takes an average 3 hours (180 minutes) to fill and 3 weeks to
empty.
Fill rate
Therefore SLOW response rate (0.1 m/minute) can be selected.
Quick Start Parameter
Vessel
Response Rate
Units
Operation
Low Calibration Point
High Calibration Point
Wizard Complete
60
= 0.08 m/minute [(Low Cal Pt. minus High Cal Pt.) / fastest of fill or empty time]
= (15.5 m – 1 m) / 180 min.
= 14.5 m /180 min. = 0.08 m/min.
sensor reference point
high calibration point
1.0 m
15.5 m
level
low calibration point
Setting
Description
STEEL
Selects vessel construction material.
SLOW
Resets fill rate and empty rate to 0.1 m/minute.
m
Sensor measurement units.
LEVEL
Material level referenced from low calibration point
15.5
Process empty level.
1.0
Process full level.
FINISH
Save new settings and exit Wizard
Operating Instructions, 06/2018, A5E34648471-AE
LR560 (PROFIBUS PA)