Parameter Reference
8.2 SETUP (2.)
ECHO MARKER (2.4.5.5.)
Factory setting:
Setting range:
Purpose:
Description:
8.2.4.6

SAMPLING (2.4.6.)

Provides a method of checking the reliability of a new echo before accepting it as the valid
reading, based on numbers of samples above or below the currently selected echo.
8.2.4.7

ECHO LOCK (2.4.6.1.)

Factory setting:
Setting range:
Purpose:
Related parameters:
8.2.4.8

UP SAMPLING (2.4.6.2.)

Factory setting:
Setting range:
Purpose:
8.2.4.9

DOWN SAMPLING (2.4.6.3.)

Factory setting:
Setting range:
Purpose:
102
70%
5 to 95%
The point on the selected echo from which the measured value is taken.
Use this feature if the reported material level fluctuates slightly due to a
variable rise in the leading edge of the true echo on the Echo Profile.
Enter the value (in percent of echo height) to ensure the Echo Lock window
intersects the Echo Profile at the sharpest rising portion of the Echo Profile
representing the true echo. This value is preset to 70%.
Material Agitator
Lock Off
Maximum Verification (not recommended for radar)
Material Agitator
Total Lock (not recommended for radar)
Selects the measurement verification process.
FILL RATE/MIN (2.3.6.2.) (Page 97)
EMPTY RATE/MIN (2.3.6.3.) (Page 97)
UP SAMPLING (2.4.6.2.) (Page 102)
DOWN SAMPLING (2.4.6.3.) (Page 102)
5
1 to 50
Specifies the number of consecutive echoes that must appear above the
echo currently selected, before the measurement is accepted as valid.
2
1 to 50
Specifies the number of consecutive echoes that must appear below the
echo currently selected, before the measurement is accepted as valid.
LR560 (PROFIBUS PA)
Operating Instructions, 06/2018, A5E34648471-AE