Quick Start wizard via SIMATIC PDM

The graphic Quick Start Wizard provides an easy step-by-step procedure that configures the
device for a simple application.
Please consult the operating instructions or online help for details on using SIMATIC PDM.
1. If you have not already done so, check that you have the most up-to-date Electronic
Device Description (EDD) for your device. [See Configuring a new device (Page 62).]
2. Launch SIMATIC Manager and create a new project. Application Guides for setting up
HART and PROFIBUS PA devices with SIMATIC PDM can be downloaded from the
product page of our website:
LR560 (www.siemens.com/LR560)
Quick start
Note
• A reset to Factory Defaults should be performed before running the Quick Start Wizard if
device has been used in a previous application. See Master Reset via SIMATIC PDM
(Page 80).
• The Quick Start wizard settings are inter-related and changes apply only after you click
on FINISH AND DOWNLOAD at the end of the last step to save settings offline and
transfer them to the device.
• Do not use the Quick Start Wizard to modify individual parameters: for quick access to
echo profile parameters, see Echo Profile via SIMATIC PDM (Page 70) or see Parameter
Reference (Page 87) for a complete list. (Perform customization only after the Quick Start
has been completed.)
• Click on BACK to return and revise settings or CANCEL to exit the Quick Start.
• For a vessel with obstructions see Auto False Echo Suppression via SIMATIC PDM
(Page 72).