Measuring accuracy
Standards applied
● IEC 61557-12
● IEC 62053-21
● IEC 62053-22
● IEC 62053-23
● EN 50470-3:
Measured variable
Voltage
Current
Apparent power
Active power
Reactive power
Total apparent power over all phases
Total active power over all phases
Total reactive power VAR1 over all phases
Cumulated active power
Cumulated reactive power
Total power factor
Line frequency
Active energy
Reactive energy
Active energy according to IEC62053-21
Reactive energy according to IEC62053-23
Measurement accuracy according to EN50470-3
Note:
For the PAC2200 (5A) device, the accuracy of the measurement depends on the quality of
the current transformers used.
Digital input
Digital input
Number
Type
Maximum switching voltage
Input current
PAC2200
Manual, 05/2018, L1V30415167B-02
"1" signal detection
"0" signal detection
Accuracy class acc. to IEC 61557-12 (K55)
Class 0.5
Class 0.5
Class 1
Class 1
Class 1
Class 1
Class 1
Class 2
Class 1
Class 2
Class 0.5
Class 0.05
Class 1
Class 2
Class 1
Class 2
Class B
1
Passive
30 V
2.5 ... 10 mA
≤0.5 mA
Technical data