CO2 Sensor Specifications

Detection technology
Detection Range
Accuracy
Response time (T90)

Temperature Sensor Specifications

Measurement technology
Measurement range
Measurement accuracy
Response time (T90)

Humidity Sensor Specifications

Measurement technology Solid state, integrated circuit
Measurement range
Measurement accuracy
Long term drift
511838
11/07
Single source dual channel, non-dispersive infrared
(NDIR)
0 to 2000 ppm, (default)
2000 to10,000 ppm
0-2000 ppm: ± 100 ppm ± 3% of reading at 25ºC
2000-10000 ppm : ± 10% of reading at 25ºC
<60 sec. (for 90% step change) for CO
ppm
Solid state, integrated circuit
-20 to 50ºC (-4 to 122ºF)
± 0.5ºC at 25ºC
30 sec.
0 to 99% RH non-condensing
± 3% RH at 25ºC, at 50% RH
less than 0.5% RH/yr