General Technical Specifications

CO2 Sensor Specifications

Detection technology
Detection Range
Accuracy
Response time (T90)

Temperature Sensor Specifications

Measurement technology
Measurement range
Measurement accuracy
Response time (T90)

Humidity Sensor Specifications

Measurement technology
Measurement range
Measurement accuracy
Long term drift
26
Single source, dual channel, non-dispersive
infrared (NDIR)
0 to 2000 ppm, (default)
0 to10,000 ppm
0-2000 ppm: 100 ppm + 3% of reading at 25ºC
2000-10000 ppm : ± 10% of reading at 25ºC
<60 sec. (for 90% step change)
for CO
0-2000 ppm
2
Solid state, integrated circuit
-20 to 50ºC (-4 to 122ºF)
± 0.5ºC at 25ºC
30 sec.
Solid state, integrated circuit
0 to 99% RH non-condensing
± 3% RH at 25ºC, at 50% RH
less than 0.5% RH/yr