Download Print this page

Installation; Setpoint Range Limiting - Regin PULSER-M Manual

Hide thumbs Also See for PULSER-M:

Advertisement

Available languages

Available languages

PULSER-M
153
93
40
K 1 2 U 3 4 U K G G
Fig 1
1 2 3 4
G G
Fig 2
1 2 3 4
G G
G G
TG-K3xx
TG-G1xx
Fig 3
1 2 3 4
G G
G G
TG-R4xx
1
3
Fig 4
Box 116 428 22 KÅLLERED SWEDEN
Tel +46 (0)31 720 02 00 Fax +46 (0)31 720 02 50
INSTRUCTIONS
i
Read this instruction before installation
and wiring of the product
Consult documentation in all cases where this
symbol is used, in order to find out the nature of
the potential hazards and any actions to be taken
Triac controller for proportional control of
electric heating, with min- / max-limiting
function
PULSER-M is a complete proportional controller for electric heating.
It has automatic voltage adjustment and can be used with either
built-in sensor or external sensor. PULSER-M pulses the whole load
On - Off. The ratio between On-time and Off-time is varied 0 - 100%
to suit the prevailing heat demand. The current is always switched at
zero phase angle to prevent RFI. It also has an input for a separate
sensor for maximum or minimum limiting the supply air temperature
during room temperature control.
PULSER-M is only intended for electric heating control. The control
principle makes it unsuitable for motor- or lighting control.
PULSER-M cannot control 3-phase loads.

Installation

Remove the front. The locking screw is be-hind the set-point knob.
Mount PULSER-M vertically, with the cooling flange at the top. Use
screws with a maximum head diameter of 5.5mm.
If PULSER-M is to be used with the internal sensor, mount it approx.
5ft above floor level at a location with a representative temperature.
The air must be able to circulate freely around the PULSER-M wit-
hout disturbances from doors, furniture etc.
PULSER-M emits approx. 20W of heat which must be dissi-
pated. Maximum ambient temperature at full load is 30°C.
Ambient temperature 0 - 30°C non-condensing.
Degree of protection: IP20.
Wiring
Supply voltage (fig 1)
Terminals 1 and 2. Not polarity sensitive.
Supply voltage: 200 - 415V AC, 50 - 60 Hz with automatic voltage
adjustment.
Maximum current 16A.
INSTRUCTIONS
The supply voltage to PULSER-M should be wired via an
all-pole switch with a minimum contact gap of 3mm. The cooling
flange is live.
Load (fig 1) Terminals 3 and 4.
Resistive single- or two-phase heater
Maximum load: 3680W at 230V (16A)
6400W at 400V (16A)
Minimum load: 230W at 230V (1A)
400W at 400V (1A)
External sensor and set-point (figs 2 - 6)
Terminals G and G. Not polarity sensitive.
When using external set-point and/or sensor the equivalent
function in the PULSER-M must be disabled. This is done by
setting the DIP-switches to the right of the terminal strip accord-
ing to the relevant figure.
Night set-back (fig 7) Terminal K and K.
Potential-free closure will give a night set-back of 0 - 10K. Set-
table with a potentiometer in the PULSER-M.
Minimum/maximum limit (figs 8 and 9)
Terminals M and M. Not polarity sensitive.
Choose function with the switches. Set the limiting temperature
on the min/max-potentiometer next to the MM terminals. Fully
counter-clockwise equals the low end temperature of the sensor
and fully clockwise equals the upper end temperature. 3 K per
division.
Switch 3 and 4 should be in the lower position if the minimum/
maximum limit function is not used.
The PULSER-M sensors have high potential compared to
neutral and earth (>200V). Thus, wiring and installation of the
sensors must comply with local codes for line voltage installa-
tions.

Setpoint range limiting

The setpoint range can be mechanically limited using the limiting
rings behind the setpoint knob.
Set the knob to a temperature within the desired limiting range.
Pull off the knob.
Loosen the screw locking the two rings. Rotate the blue ring so
that the protruding part is slightly lower than the lower tempera-
ture limit. Use the markers on the bottom of the covers knob-
cutout as an aid. The markers are 5° apart.
In the same way set the red ring to a value slightly higher than
the upper limit temperature. Retighten the locking screw without
disturbing the position of the rings. Replace the knob and check
the result. Make fine adjustments if necessary.

Advertisement

loading