Output - Siemens LOGO!Power 6EP1311-1SH13 Operating Instructions Manual

Hide thumbs Also See for LOGO!Power 6EP1311-1SH13:
Table of Contents

Advertisement

6.2

Output

Rated voltage
Total tolerance
Static line smoothing
Static load smoothing
Residual ripple
Spikes (bandwidth: 20 MHz)
Setting range
Response on activation/deactivation
Startup delay/voltage rise
Rated current Ia rated
Current range
Power reserve
Parallel switching for enhanced performance
Output characteristic
LOGO!Power
Operating Instructions, 02.2011, C98130-A7560-A999-1-7619
V
a rated
Up to +55 °C
Derating
Controlled, isolated DC voltage
5 V DC, 12 V, 15 V or 24 V
±3 %
Approx. ±0.5 %
Approx. ±1 %
12 V, 15 V, 24 V < 200 mVpp
5 V < 100 mVpp
12 V, 15 V, 24 V < 300 mVpp
5 V < 100 mVpp
5 V 4.6 to 5.4 V
12 V 10.5 to 12.9 V
15 V 13.9 to 16.1 V
24 V 22.2 to 26.4 V
No overshoot of Va (soft start)
< 1.5 s/< 500 ms (typ. 70 ms/typ. 10
ms) (see the figure below)
6EP1311-1SH03 3 A
6EP1311-1SH13 6.3 A
6EP1321-1SH03 1.9 A
6EP1322-1SH03 4.5 A
6EP1351-1SH03 1.9 A
6EP1352-1SH03 4 A
6EP1331-1SH03 1.3 A
6EP1332-1SH43 2.5 A
6EP1332-1SH52 4 A
0 ... 100% Ia rated
0 ... 70% Ia rated (at +70 °C)
When you turn on the power supply 1.5 x Ia rated
for typ. 200 ms
Yes, 2 units
(see illustration below)
Technical data
6.2 Output
25

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents