General
NOTICE
Damage to the du/dt filter compact by using components that have not been released
When using components that have not been released, damage or malfunctions can occur
at the devices or the system itself.
• Only use a du/dt filter compact that SIEMENS has approved for operation with
NOTICE
Damage to the du/dt filter compact during continuous operation with low output frequencies
Continuous operation at an output frequency less than 10 Hz can produce thermal overload
and destroy the dv/dt filter.
• Do not operate the drive when using a dv/dt filter compact plus Voltage Peak Limiter
• You may operate the drive for a maximum load duration of 5 minutes at an output
NOTICE
Damage to the du/dt filter compact if it is not activated during commissioning
The du/dt filter compact may be damaged if it is not activated during commissioning.
• Activate the du/dt filter compact during commissioning via parameter p0230 = 2. The
NOTICE
Damage to the du/dt filter compact if a motor is not connected
Du/dt filters compact which are operated without a motor being connected can be damaged
or destroyed.
• Never operate a du/dt filter compact connected to the Power Module without a
Note
Cable lengths
Keep the connecting cables to the Power Module as short as possible (max. 5 m). Use an
equivalent cable type when replacing the cables supplied.
12
SINAMICS.
continuously with an output frequency less than 10 Hz.
frequency less than 10 Hz, provided that you then select an operation with an output
frequency higher than 10 Hz for a period of 5 minutes.
pulse frequency will then be limited automatically to permissible values following this.
connected motor.
dV/dt filter compact plus Voltage Peak Limiter
Operating Instructions, 04/2016, A5E32847614B AC