Download Print this page

Siemens SINAMICS G120P Operating Instructions Manual page 31

Du/dt filter compact plus voltage peak limiter for power modules pm330
Hide thumbs Also See for SINAMICS G120P:

Advertisement

Table 6- 4
Technical data of the du/dt filters plus Voltage Peak Limiter, 3 AC 500 V – 690 V
Article number
I
thmax
Degree of protection
Power loss
- at 50 Hz
- at 60 Hz
Max. permissible cable
length between du/dt filter
and motor
du/dt reactor
Terminals
- 1U1/1V1/1W1
- 1U2/1V2/1W2
- PE
Dimensions
Width
Height
Depth
Weight, approx.
Voltage Peak Limiter
Terminals
- DCPS/DCNS
- 1U2/1V2/1W2
- PE
Dimensions
Width
Height
Depth
Weight, approx.
dV/dt filter compact plus Voltage Peak Limiter
Operating Instructions, 04/2016, A5E32847614B AC
6SL3000-
2DG38-1EA0
A
810
IP00
kW
0.964
kW
0.998
m
for 2 x M12 bolts
for 2 x M12 bolts
M6 screw
mm
430
mm
385
mm
323
kg
171.2
for M8 bolts
for M8 bolts
for M6 screw
mm
277
mm
360
mm
291
kg
18.8
Technical specifications
100 (shielded)
150 (unshielded)
31

Advertisement

loading