Electrical - Mira Azora Installation And User Manual

Electric shower
Table of Contents

Advertisement

The appliance is fitted with a brass inlet compression assembly for connecting
to a 15 mm supply pipe from the top, bottom or back. Double checkvalves, if
fitted in the inlet supply to the appliance, can cause a pressure build-up, which
could exceed the maximum static inlet pressure and damage the appliance.

2. Electrical

In a domestic installation, the rating of the electricity supplier's fuse and the
consumer unit must be adequate for the additional demand. All Mira electric
showers are high power units, it is essential to contact your electricity supplier
to ensure that the supply is adequate for the product.
Voltage drop due to local heavy demand will reduce the shower's
performance.
The appliance MUST BE EARTHED by connecting the supply-cable earth
conductor to the earth terminal.
SUPPLEMENTARY BONDING: Within the bathroom or shower room, all
accessible conductive parts of electrical equipment and extraneous conductive
parts (metal parts) that are likely to introduce earth potential, must be
electrically bonded to earth using a minimum cable size of 4.0 mm² if the cable
is not mechanically protected, (2.5 mm² if mechanically protected).
The minimum cable size (cross-sectional area) required should be in
accordance with BS 7671.
As a guide only, and in accordance with BS 7671 we recommend close circuit
protection: i.e. 9.8 kW = 45 Amp
A 30 mA Residual Current Device (RCD) MUST be included in the electrical
circuit. This may be part of the consumer unit or a separate unit.
A separate, permanently connected supply must be taken from the consumer
unit to the appliance through a double-pole switch, which has at least 3 mm of
contact separation. The switch can be a ceiling mounted pullcord type within
the shower room, or a wall mounted switch in an adjacent room.
DO NOT twist the individual cable cores of either the live or neutral conductors,
as this will prevent them from entering the terminal block.
DO NOT exert strain on the terminal block. Ensure that the electrical
connections are tightly screwed down.
DO NOT turn-on the electrical supply until the plumbing has been
completed.
9