2.1.3 Australian Requirements
To be installed in accordance with AS 5601 / AG 601, local authority, gas, electricity, and any other
relevant statutory regulations.
2.2
Power Requirements
The three phase supply plug for the elements is rated at 60 amps, 250 VAC and is NEMA
configuration L15-60P. The control and filter plug is rated at 20 amps, 120/208 VAC and is NEMA
configuration L21-20P. Each fryer should have its cord for the element supply on an individual
circuit as well as the control cord.
VOLTAGE
208
240
480
220/380
240/415
230/400
If this appliance is permanently connected to fixed wiring, it must be connected by
means of copper wires having a temperature rating of not less than 167°F (75°C).
This appliance must be connected to a power supply having the same voltage and
phase as specified on the rating plate located on the inside of the appliance door.
All wiring connections for this appliance must be made in accordance with the
wiring diagram(s) furnished with the appliance.
affixed to the inside of the appliance door when installing or servicing this
equipment.
2.3
After Fryers Are Positioned At the Frying Station
No structural material on the fryer should be altered or removed to accommodate
placement of the fryer under a hood. Questions? Call the Frymaster Service Hotline
at 1-800-551-8633.
1. Once the fryer has been positioned at the frying station, use a carpenter's level placed across the
top of the frypot to verify that the unit is level, both side-to-side and front-to-back.
To level fryers, adjust the casters being careful to ensure the fryer(s) are at the proper height in
the frying station.
WIRE
MIN.
PHASE
SERVICE
SIZE
3
3
3
3
3
3
3
4
3
4
3
4
NOTICE
AWG
2
(mm
)
L1
6
(16)
39
6
(16)
34
8
(10)
17
6
(16)
21
6
(16)
20
6
(16)
21
DANGER
DANGER
Refer to the wiring diagram(s)
DANGER
2-3
AMPS PER LEG
L2
L3
39
39
34
34
17
17
21
21
20
21
21
21