Siemens PM250 Hardware Installation Manual page 58

Power module
Table of Contents

Advertisement

Accessories
7.1 Reactor and filter
Installing the output reactor as lateral mounting component
The output reactors for Power Modules with a rated power (HO) of more than 11 kW have to
be mounted laterally.
Figure 7-5
For more information see http://support.automation.siemens.com/WW/view/en/22103628
Technical specifications of the output reactors
The major electrical specification of the output reactors is the same as for the suitable Power
Module. This applies to:
● voltage
● rated current
The maximum permissible output frequency of the Power Module is 150 Hz when an output
reactor is used – the pulse frequency must not exceed 4 kHz.
The admissible ambient conditions of the output reactors are the same as for the suitable
Power Module. This applies to:
● storage and transport temperature
● operating temperature
● relative humidity
● shock and vibration load
58
Connecting the output reactor as lateral component
Hardware Installation Manual, 09/2012, A5E01003502B AD
PM250 Power Module

Hide quick links: