Technical specifications

Common performance ratings of the Power Module
Table 6- 1
Feature
Line operating voltage
Input frequency
Modulation depth
Power factor λ
Overload capability (HO)
5.5 kW ... 75 kW
Overload capability (LO)
7.5 kW ... 90 kW
Inrush current
Pulse frequency
Electromagnetic
compatibility
Braking
Protection level
Temperature range
without derating (HO)
Temperature range
without derating (LO)
Temperature range with
derating
Storage temperature
Humidity
Pollution
PM250 Power Module
Hardware Installation Manual, 09/2012, A5E01003502B AD
Performance ratings
Specification
3 AC 380 V ... 480 V ± 10%
The permissible voltage depends on the operational altitude
47 Hz ... 63 Hz
87% (The maximal output voltage is 87% of the input voltage)
0.9
1.5 x Nominal output current (150% overload) for 57 s every 300 s
2 x Nominal output current (200% overload) for 3 s every 300 s
1.1 x Nominal output current (110% overload) for 57 s every 300 s
1.5 x Nominal output current (150% overload) for 3 s every 300 s
Less than rated input current
4 kHz standard
The pulse frequency can be changed manually in 2 kHz steps.
Increasing the pulse frequencies above standard leads to an output
current reduction.
Power Modules with untegrated class A filters according to EN 55011
available.
Dynamic braking with regeneration (up to 100% output rating)
IP20
5.5 kW ... 75 kW
0 °C ... +50 °C (14 °F ... 122 °F)
0 °C ... +40 °C (14 °F ... 104 °F)
Higher operational temperature is possible with power derating
-40 °C ... +70 °C (-40 °F ... 158 °F)
< 95% RH - non-condensing
In areas of high relative humidity, measures should be taken to ensure
that condensation does not form within or around the SINAMICS G120.
Anti-condensation heaters are commonly used to prevent the formation of
condensation.
According pollution degree level 2
Do not install the SINAMICS G120 in an environment which contains
atmospheric pollutants such as dust and/or corrosive gases.