Siemens SIMATIC ET 200SP Manual page 19

Digital input module, di 8x24vdc hf 6es713106bf00-0ca0
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Parameters/address space
4.1 Parameters
Parameter
Input delay
Pulse stretching
Hardware interrupt
rising edge
Hardware interrupt
falling edge
Potential group
If you use a floating switch, you need to connect a resistor in parallel so that the wire break diagnostics is enabled in the
1
open state (sensor resistance for the wire break diagnostics: 25 kΩ to 45 kΩ).
Due to the limited number of parameters of a maximum of 244 bytes per ET 200SP station with a PROFIBUS GSD
2
configuration, the parameter assignment options are restricted. The parameter length of the I/O module is 6 bytes with
PROFIBUS GSD configuration. If necessary, you can set this parameter, however, with data records 0 to 7 or data rec-
ord 128, see Appendix "Parameter data record".
18
Value range
None
0.05 ms
0.1 ms
0.4 ms
0.8 ms
1.6 ms
3.2 ms
12.8 ms
20 ms
None
0.05 s
0.1 s
0.2 s
0.5 s
1 s
2 s
Disable
Enable
Disable
Enable
Use potential group of the
left module (module
plugged into a dark-
colored BaseUnit)
Enable new potential
group (module plugged in-
to light-colored BaseUnit)
Default
Configuration
in RUN
3.2 ms
Yes
None
Yes
Disable
Yes
Disable
Yes
Use potential
No
group of the
left module
Digital input module DI 8x24VDC HF (6ES7131-6BF00-0CA0)
Scope with configuration soft-
ware, e.g., STEP 7 (TIA Portal)
GSD file
GSD file
PROFINET IO
PROFIBUS DP
Channel
Module
2
Channel
2
Channel
2
Channel
2
Module
Module
Manual, 12/2017, A5E03576305-AE