Quick Start-Up - ABB Arc Guard System TVOC-2-COM Configuration Manual

Modbus
Table of Contents

Advertisement

Draft, ne pas diffuser Wed Dec 05 2018 12:41:51 GMT+0100 (Romance Standard Time)
8
1.1
Introduction
This manual covers the Modbus interface, which offers
a direct connection to Modbus-RTU for the Arc Guard
System™ TVOC-2.
TVOC-2-COM will behave as a slave. This means all
communication will be performed by a master device on
the same Modbus system. Mostly this will be a PLC. This
manual explains how to install the Arc Guard System™
TVOC-2-COM to your Modbus system.
1.2
References
[1] http://www.modbus.org/docs/Modbus_Application_
Protocol_V1_1b3.pdf (2012)
[2] http://www.modbus.org/docs/Modbus_over_serial_
line_V1_02.pdf (2006)
[3] https://www.modbusdriver.com/modpoll.html
1.3

Quick start-up

1
Make sure your Modbus master has been installed to
the system.
2
The TVOC-2-COM will be delivered with the following
configuration:
baud rate 19200
parity even
stop bits 1
Modbus ID 248*
*Modbus ID 248 is not a valid id for a Modbus system but is used to indicate that the
communication is disabled.
3
Physically connect the system to the Modbus network.
4
Test communication between your master and
the TVOC-2 system. For example see chapter 5
Troubleshooting.
ABB
ARC GUARD SYSTEM™ – T VOC-2- COM MODBUS CONFIGUR ATION MANUAL
START
Master
1
present
Set Modbus
2
id of TVOC-2
Connect
TVOC-2
3
System
4
Test
Ready
Figure 1
Quick start-up