ABB Arc Guard System TVOC-2-COM Configuration Manual page 29

Modbus
Table of Contents

Advertisement

Draft, ne pas diffuser Wed Dec 05 2018 12:41:51 GMT+0100 (Romance Standard Time)
The first part of the ID number is static, it is always
"1S16010".
Then byte 4, 3 and 2 follows in decimal format with 2
digits for each number.
Finally a 16-bit word constructed from byte 1 as most
significant and byte 0 as least significant is added as a 4
digit decimal number (byte 1 << 8 | byte 0).
Example: If the Arc Monitor ID registers contains the
following values:
Arc Monitor ID, byte 0
Arc Monitor ID, byte 1
Arc Monitor ID, byte 2
Arc Monitor ID, byte 3
Arc Monitor ID, byte 4
HMI SW version XXYY
The HMI is the HMI that is queried on the Modbus
network.
See 4.4.7.1 Arc Monitor SW version XXYY above.
HMI SW version ZZ
4.4.7.7
See 4.4.7.2 Arc Monitor SW version ZZ above.
HMI HW version
4.4.7.8
See 4.4.7.3 Arc Monitor HW version above.
HMI ID, byte x
4.4.7.9
See 4.4.7.6 Arc Monitor ID, byte x above.
Other HMI SW version XXYY
4.4.7.10
Other HMI is the HMI that is not queried on the Modbus
network.
See 4.4.7.1 Arc Monitor SW version XXYY above.
Other HMI SW version ZZ
4.4.7.11
See 4.4.7.2 Arc Monitor SW version ZZ above.
Other HMI HW version
4.4.7.12
See 4.4.7.3 Arc Monitor HW version above.
Other HMI ID, byte x
4.4.7.13
See 4.4.7.6 Arc Monitor ID, byte x above.
X2 HW version
4.4.7.14
See 4.4.7.3 Arc Monitor HW version above.
X2 CPLD version XXYY
4.4.7.15
See 4.4.7.4 Arc Monitor CPLD version XXYY above.
ABB
ARC GUARD SYSTEM™ – T VOC-2- COM MODBUS CONFIGUR ATION MANUAL
0x00D9
0x0007
0x0012 (18)
0x000E (14)
0x0048 (72)
This corresponds to ID
1S16010
72
14
18
0x48
0x0E
0x12
29
2009
0x07D9