Available Registers - ABB Arc Guard System TVOC-2-COM Configuration Manual

Modbus
Table of Contents

Advertisement

Draft, ne pas diffuser Wed Dec 05 2018 12:41:51 GMT+0100 (Romance Standard Time)
4.3.2
Write Registers (06, 16)
Functions 06, Write Single Register and function 16, Write
Multiple Registers, are supported.
Table 4
Write Exceptions
Possible exception responses
Code
02
03
4.3.3

Available registers

Modbus registers are numbered from 1 to 65536.
In a Modbus PDU (Protocol Data Unit) these registers are
addressed from 0 to 65535.
The following table lists the available parameters. More
details about the data format can be found in
4.4 Register data format below.
Modbus registers
Parameter name
Trip 1 detector, low
Trip 1 detector, low
Trip 1 detector, high
Trip 1 relay
Trip 1 date
Trip 1 time HHMM
Trip 1 time SS
Trip 2 detector, low
Trip 2 detector, high
Trip 2 relay
Trip 2 date
Trip 2 time HHMM
Trip 2 time SS
Trip 3 detector, low
Trip 3 detector, high
Trip 3 relay
Trip 3 date
Trip 3 time HHMM
Trip 3 time SS
Trip 4 detector, low
Trip 4 detector, high
Trip 4 relay
Trip 4 date
Trip 4 time HHMM
Trip 4 time SS
Trip 5 detector, low
Trip 5 detector, high
Trip 5 relay
Trip 5 date
Trip 5 time HHMM
Trip 5 time SS
Trip 6 detector, low
Trip 6 detector, high
ABB
ARC GUARD SYSTEM™ – T VOC-2- COM MODBUS CONFIGUR ATION MANUAL
Name
ILLEGAL_DATA_ADDRESS
ILLEGAL_DATA_VALUE
Access
PDU Address
Hex
R
0x0064
R
0x0064
R
0x0065
R
0x0066
R
0x0067
R
0x0068
R
0x0069
R
0x006B
R
0x006C
R
0x006D
R
0x006E
R
0x006F
R
0x0070
R
0x0072
R
0x0073
R
0x0074
R
0x0075
R
0x0076
R
0x0077
R
0x0079
R
0x007A
R
0x007B
R
0x007C
R
0x007D
R
0x007E
R
0x0080
R
0x0081
R
0x0082
R
0x0083
R
0x0084
R
0x0085
R
0x0087
R
0x0088
Meaning
Address refers to a register that is not available
or not readable.
The value written is not permitted for this
register.
Register Number
Dec
Hex
Dec
100
0x0065
101
100
0x0065
101
101
0x0066
102
102
0x0067
103
103
0x0068
104
104
0x0069
105
105
0x006A
106
107
0x006C
108
108
0x006D
109
109
0x006E
110
110
0x006F
111
111
0x0070
112
112
0x0071
113
114
0x0073
115
115
0x0074
116
116
0x0075
117
117
0x0076
118
118
0x0077
119
119
0x0078
120
121
0x007A
122
122
0x007B
123
123
0x007C
124
124
0x007D
125
125
0x007E
126
126
0x007F
127
128
0x0081
129
129
0x0082
130
130
0x0083
131
131
0x0084
132
132
0x0085
133
133
0x0086
134
135
0x0088
136
136
0x0089
137
21
Remark
X1:1 – X2:5
X1:1 – X2:5
X2:6 – X3:10
K4 (LSb), K5, K6
Days since January 1, 1970
MSB = hours, LSB = minutes
X1:1 – X2:5
X2:6 – X3:10
K4 (LSb), K5, K6
Days since January 1, 1970
MSB = hours, LSB = minutes
X1:1 – X2:5
X2:6 – X3:10
K4 (LSb), K5, K6
Days since January 1, 1970
MSB = hours, LSB = minutes
X1:1 – X2:5
X2:6 – X3:10
K4 (LSb), K5, K6
Days since January 1, 1970
MSB = hours, LSB = minutes
X1:1 – X2:5
X2:6 – X3:10
K4 (LSb), K5, K6
Days since January 1, 1970
MSB = hours, LSB = minutes
X1:1 – X2:5