Alarm Mode (Ald1 / Ald2 / Ald3) - Taie FA Series Operation Manual

Digital pid controller
Hide thumbs Also See for FA Series:
Table of Contents

Advertisement

11.3

Alarm mode (ALD1 / ALD2 / ALD3)

(
:SV
Deviation high alarm
with hold action*
01
OFF
Deviation high alarm
11
OFF
Deviation low alarm
with hold action*
02
ON
Deviation low alarm
12
ON
Deviation high/low alarm
with hold action*
03
ON
OFF
LOW
Deviation high/low alarm
13
ON
OFF
LOW
Band alarm
04
OFF
ON
14
LOW
Process high alarm
with hold action*
05
OFF
LOW
Process high alarm
15
OFF
LOW
*Hold action:
When Hold action is ON ,the alarm action is suppressed at start-up until the measured
value(PV) enters the non-alarm range.
*System failed:
It means that the controller display error message with one of following :
"UUU1" or "NNN1" or "CJCE"
:Alarm set value)
ON
PV
HIGH
ON
PV
HIGH
OFF
PV
HIGH
OFF
PV
HIGH
ON
PV
HIGH
ON
PV
HIGH
OFF
PV
HIGH
ON
PV
HIGH
ON
PV
HIGH
Process low alarm
with hold action*
06
ON
LOW
Process low alarm
16
ON
LOW
Segment End alarm
(Only for Programmable controller)
(1) ALD1~3 , set 07
(2) ALD1~3=Alarm Segment
07
(3) ALT1~3 defines as follows:
0
=flicker alarm
99.59
others
Program Run alarm
(Only for Programmable controller)
17
Run
ON
System failed alarm* (ON)
08
Normal
OFF
System failed alarm* (OFF)
18
Normal
ON
Heater Break Alarm
Heater Break Alarm
(HBA)
09
Please refer with HBA function
Please refer with HBA Function
Description in Page39
description in page 31.
00
No alarm
10
RAMP & SOAK
If PV=SV, Alarm will delay for a
while then (alarm set value) action.
Range: 00.00~99.59(hr.min.)
38
OFF
PV
HIGH
OFF
PV
HIGH
=continued alarm
=alarm ON time
Stop
OFF
AL
Failed
ON
AL
Failed
OFF
AL
(HBA)