Earth ground clamp
Hide thumbs Also See for 1630-2:
Table of Contents

Advertisement

2.
Verify that the display reading is within specification, see
Table 4.
If the reading is not within specification, clean the
heads of the Jaw and repeat step 1 and step 2.
If the reading is within specification, remove the Jaw
from the Standard Loop Resistance. The Clamp is
ready for a ground resistance measurement.
Table 4. Display Reading Specifications
Input (Ω)
Minimum
0.474
0.417
0.5
0.443
10
9.55
100
96.0
For ground resistance measurements:
1.
2.
3.
4.
5.
Maximum
0.531
0.558
10.45
104.0
Open the jaw and make sure the jaw is free of dust, dirt, or
any foreign substances.
Turn on the Clamp.
Push  to select the Ω function.
Attach the Clamp to the electrode or ground rod to be
measured.
Read the value of R
(ground resistance) from the
g
display. Figure 8 illustrates the ground resistance
measurement principles.
Earth Ground Clamp
How to Use the Clamp
13