Parameters
Reaction to CPU STOP •
Potential group
Due to the limited number of parameters at a maximum of 244 bytes per ET 200SP station with a PROFIBUS GSD
1
configuration, the configuration options are restricted. If required, you can assign these parameters using data rec-
ord 128 as described in the "GSD file PROFINET IO" column (see table above). The parameter length of the I/O module
is 32 bytes.
Note
• If both parameters "Diagnostics: short-circuit to L+" and "Diagnostics: wire break" are
enabled and one of these diagnostic events occurs, the affected channel is switched off.
This prevents undefined load switching and the corresponding diagnostic alarm is
triggered.
• If both parameters "Diagnostics: short-circuit to L+" and "Diagnostics: wire break" are
enabled and one of these diagnostic events occurs, the affected channel is switched off.
This prevents undefined load switching and the corresponding diagnostic alarm is
triggered.
• If the parameter "Diagnostics: short-circuit to L+" is enabled and "Diagnostics: wire break"
is disabled, the signal status is retained at the affected channel when "Diagnostics: short-
circuit to L+" occurs. A diagnostic alarm is triggered only for 0 signal.
Digital output module DQ 16x24VDC/0.5A ST (6ES7132-6BH01-0BA0)
Manual, 09/2017, A5E03574420-AE
Range of values
Turn off
Keep last value
Output substitute
value 1
Use potential group of
the left module (mod-
ule plugged into a
dark-colored Ba-
seUnit)
Enable new potential
group (module
plugged into light-
colored BaseUnit)
Default
Parameter
reassign-
ment in
RUN
Turn off
Yes
Use potential
No
group of the left
module
Parameters/address space
4.1 Parameters
Scope with configuration software,
e.g. STEP 7 (TIA Portal)
GSD file
GSD file
PROFINET IO
PROFIBUS DP
Channel
Module
Module
Module
1
17