Siemens SIMATIC ET 200SP Manual page 22

Digital output module, dq 16x24vdc/0.5a st, 6es7132-6bh01-0baq
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Interrupts/diagnostic alarms
5.1 Status and error display
Meaning of the LEDs
The following tables contain the meaning of the status and error displays. Remedial
measures for diagnostic alarms can be found in chapter Diagnostic messages (Page 24).
DIAG LED
Table 5- 1
DIAG LED
LED channel status
Table 5- 2
LED channel
PWR LED
Table 5- 3
PWR LED
22
DIAG LED fault display
Meaning
Backplane bus supply of the ET 200SP not OK
Off

Module not configured
Flashing
Module parameters assigned
On
Module diagnostics is available
Flashing
LED channel status display
Meaning
status
Channel deactivated or activated and process signal = 0
Off

Channel activated and process signal = 1
On
Status display of the PWR LED
Meaning
Supply voltage L+ missing
Off

Supply voltage L+ present
On
Digital output module DQ 16x24VDC/0.5A ST (6ES7132-6BH01-0BA0)