Management Interfaces; Management Interfaces 1.8.1 V.24 Interface (External Management); Usb Interface - Hirschmann OCTOPUS OS3 User Manual

Managed ethernet switch
Table of Contents

Advertisement

1.8

Management interfaces

1.8.1
V.24 interface (external management)
This interface is a 4-pin, "A"-coded M12 socket.
The V.24 interface is a serial interface for the local connection of an external
management station (VT100 terminal or PC with corresponding terminal
emulation). This allows you to set up a connection to the Command Line
Interface (CLI) and to the system monitor.
VT100 terminal settings
Speed
Data
Stopbit
Handshake
Parity
The socket housing is electrically connected to the front panel of the device.
The V.24 interface is electrically insulated from the supply voltage.
1.8.2

USB interface

This interface is a 5-pin, "A"-coded M12 socket with shielding.
The USB interface allows you to connect the AutoConfiguration Adapter
ACA21-M12/ACA22-M12 storage medium. This is used for saving/loading
the configuration data and diagnostic information, and for loading the
software.
The USB interface has the following properties:
Supplies current of max. 500 mA
Voltage not potential-separated
Supports the USB master mode
Supports USB 2.0
20
9600 Baud
8 bit
1 bit
off
none
Installation OCTOPUS OS3
Release 01 02/2019

Advertisement

Table of Contents
loading