Electrical Connections - Hamworthy Purewell VariHeat he Installation, Commisioning And Maintenance Instructions

Cast iron, pre-mix, modular boilers with automatic ignition for heating and domestic hot water installations
Hide thumbs Also See for Purewell VariHeat he:
Table of Contents

Advertisement

Open Vented Systems
Boilers must not be capable of isolation from the vent pipe. Valves between boiler and vent pipe to be three way
type such that when boiler is isolated from vent pipe it is open to atmosphere. Safety valves should be mounted
on the boiler using the connection provided.
Sealed Systems
Boilers must not be capable of isolation from the safety valve. Valves between boiler and safety valve to be three
way type such that when boiler is isolated from safety valve it is open to atmosphere. Hamworthy Heating Ltd
provide a connection on the boiler for the safety valve .
Where using Hamworthy Heating Ltd pipework kits, assembly of these is detailed in the Instruction manual
supplied with kit.

5.3 Electrical Connections:

The following electrical connections are provided on each module on a rail at the base of the front of the boiler.
Supply: Live, Neutral and Earth. See Section 4.6 for details.
Live and Neutral connections for Shunt pump or Primary Pump
Boiler Overheat Fault Alarm Signal Output
Common Fault ie A Boiler Ignition Lockout Or Fault Alarm Signal Output
Boiler Normal Run Signal Output
Remote On/Off
0-10v Analogue Control Signal Input
External sensors
Cascade Management of Multiple Boiler Installations