Mounting With A Welding Type Adapter; Mounting With A Clamp Type Adapter - Siemens SITRANS F M MAG 1100 Operating Instructions Manual

Electromagnetic flowmeter sensor
Hide thumbs Also See for SITRANS F M MAG 1100:
Table of Contents

Advertisement

4.6.1

Mounting with a welding type adapter

To mount a MAG 1100 F with welding type adapters, follow these steps:
1. Cut a piece out of the pipeline equal to the built-in length "L".
2. Assemble the sensor and the adapters with the clamp rings. Leave the gaskets off.
3. Mount the sensor and stitch weld the adapters to the pipe.
4. Remove the clamp rings and dismount the sensor.
5. Ensure that the adapters are firmly welded to the pipe.
6. Remount the sensor with gaskets and clamp rings.
4.6.2

Mounting with a clamp type adapter

To mount a MAG 1100 F with clamp type adapters, follow these steps:
1. Prepare the pipeline with a suitable fitting.
2. Assemble the sensor and adapters together with the gaskets.
3. Place the clamp rings around the clamp connections between the adapters and pipeline.
4. Close and tighten the clamp rings.
SITRANS F M MAG 1100 sensor
Operating Instructions, 01/2018, A5E03433301-AC
Installing/Mounting
4.6 Mounting MAG 1100 F
29