Installation In Partially Filled Pipes - Siemens SITRANS F M MAG 1100 Operating Instructions Manual

Electromagnetic flowmeter sensor
Hide thumbs Also See for SITRANS F M MAG 1100:
Table of Contents

Advertisement

Note
Empty pipe detection
For applications with empty pipe detection, the sensor can be tilted 45°, as shown above.
4.3

Installation in partially filled pipes

Installation in partially filled pipes
For partially filled pipes or pipes with downward flow and free outlet the flowmeter should be
located in a U-tube.
Installation in large pipes
The flowmeter can be installed between two reducers (for example DIN 28545). At α ≤ 8° the
following pressure drop curves apply. The curves are applicable to water.
SITRANS F M MAG 1100 sensor
Operating Instructions, 01/2018, A5E03433301-AC
Installing/Mounting
4.3 Installation in partially filled pipes
21